Electrical Connection
Before working on the unit, switch off the power supply and secure it against being switched on again! Check that there
is no power flowing! Electrical connections may only be made by a specialist and in compliance with the applicable
regulations. The unit may not be put into operation if there is visible damage to the housing, e.g. cracks.
The unit may not be accessible from behind.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed
temperature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand
side.
The customer must provide an all-pole disconnecting device, e.g. an emergency heating switch.
The cables being connected to the unit must not be stripped by more than 55 mm, and the cable jacket must reach into
the housing just to the other side of the strain relief.
Installing the Temperature Sensors
The controller operates with Pt1000 temperature sensors which are accurate to 1 °C, ensuring optimal control of system func-
tions.
If desired, the sensor cables can be extended to a maximum of 30 m using a cable with a cross-section of at least
0.75 mm². Ensure there is no contact resistance! Position the sensor precisely in the area to be measured! Only use
immersion, pipe-mounted or flat-mounted sensors suitable for the specific area of application with the appropriate
permissible temperature range.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed
temperature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand
side.
Temperature Resistance Table for Pt1000 Sensors
°C -20 -10 0 10 20 30 40 50 60 70 80 90 100
Ω 922 961 1000 1039 1077 1116 1155 1194 1232 1270 1308 1347 1385