C. Outdoor- and Indoor-Fan Motor Bearings
The outdoor- and indoor-fan motors have permanently-
sealed bearings, so no field lubrication is necessary.
NOTE: Field-supplied motors with removable lubrication plug
should be lubricated every 6 months.
III. INDOOR FAN PERFORMANCE ADJUSTMENT
(Fig. 25, 28, 29)
Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speeds:
1. Shut off unit power supply.
2.a. Size 150 only: Loosen belt by loosening carriage nuts
holding motor mount assembly to fan scroll side plates
(A and B).
b. Size 180 only: Loosen nuts on the 2 carriage bolts in
the mounting base. Install jacking bolt and plate un-
der motor base (bolt and plate are shipped in install-
ers packet). Using bolt and plate, raise motor to top
of slide and remove belt. Secure motor in this position
by tightening the nuts on the carriage bolts.
3. Loosen movable-pulley flange setscrew (see Fig. 25).
4. Screw movable flange towardfixedflange to increase speed
and away from fixed flange to decrease speed. Increas-
ing fan speed increases load on motor. Do not exceed maxi-
mum speed specified in Table 1.
See Table 10 for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)
6. Replace and tighten belts (see Belt Tension Adjustment
section on page 15).
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mount-
ing plate.
Table 10 Air Quantity Limits
UNIT
542J
MINIMUM
CFM
MAXIMUM
CFM
150 3750 6250
180 4500* 7500
*Minimum cfm is 5600 when electric heat is used.
Fig. 27 Compressor Sight Glass Oil Level
Fig. 28 542J150 Indoor-Fan Motor Adjustment
NOTE: A3
1
2
-in. bolt and threaded plate are included in the installer’s
packet. They can be added to the motor support channel below the mo-
tor mounting plate to aid in raising the motor.
Fig. 29 542J180 Indoor-Fan Motor Section
—21—