APPLICATION DATA
Condensate trap A 2 -- in. (51 mm) condensate trap must be
field supplied.
Ductwo rk Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge Units are equipped
with factory -- installed inserts in the down -- flow openings. Removal
of the inserts is similar to removing an electrical knock-- out. Use
the duct cover to seal the horizontal discharge openings in the unit.
Units installed in horizontal discharge orientation do not require
duct covers.
Airflow Units are draw -- thru in the cooling mode and
blow--thru in the heating mode.
Maximum cooling airflow To minimize the possibility of
condensate blow-- off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow Minimum cooling airflow is 350
cfm per ton.
Minimum ambient cooling operation temperature —All
standard units have a minimum ambient operating temperature of
40_F(4_C). With accessory low ambient temperature kit, units can
operate at temperatures down to 0_F(--17_C).
Minimum temperature Air entering the heat exchanger in
heating mode must be a minimum of 50_F(10_C) continuous
and/or 45_F(7_C) intermittent.
574D-- -- A