52
A12191
6.3.8.1. Disable Zoning
This option allows the installer to enable or disable zoning. After the
selection is made, touch SAVE.
Disable Zoning: Yes or No. Default = No
6.3.8.2. Zone Offsets
This option allows actual temperature offset for each zone, allowing
calibration (or deliberate miscalibration) of each sensor. Use the Left (<)
or Right (>) buttons to change the zone. After the selection is made,
touch SAVE.
Temperature Offset: Adjustable between -5 to 5°F (-3 to 3°C).
Default = 0°F
6.3.8.3. Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to
select the maximum allowable noise/airflow relationship into each zone
based on air noise and comfort requirements. LOW means 100% of
maximum assessed airflow; MED-LOW means 138% of maximum
assessed airflow; MEDIUM means 176% of maximum assessed airflow;
MED-HIGH means 214% of maximum assessed airflow; HIGH means
250% of maximum assessed airflow; and NO LIMIT means the