EasyManuals Logo

Bryant HRVBBLHA User Manual

Bryant HRVBBLHA
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
19
BLK BLACK
BLU BLUE
BRN BROWN
GRN GREEN
GRY GRY
ORG ORANGE
RED RED
WHT WHITE
YEL YELLOW
COLOR CODE
CONNECTION DIAGRAM
123
456
789
123
345
6789
J3
J2J1
J4
FFIOCOL BRYG
FAN MOTOR 2
(Note 2)
FAN MOTOR 1
DAMPER MOTOR 2
(Note 3)
DAMPER MOTOR 1
21 21
120V, 60Hz
NEMA-15P
5-15 PLUG
21 21
MOTOR
CAPACITOR
MOTOR
CAPACITOR
BRN
BRN
BRN
BRN
GRY
ORG
BLU
RED
GRY
ORG
BLU
RED
YEL
BLU
YEL
BLU
BLK
WHT
GRN
GRN
NC
NC
GRY
ORG
BLU
YEL
BLK
WHT
-t
DEFROST TEMPERATURE
SENSOR
(COMMON)
(NO CONTACT)
(NC CONTACT)
BLK
GRN
RED
YEL
RED
BLK
YEL
WALL CONTROL
NOTE 1
OVERRIDE
OPTIONAL
AIR HANDLER
FAN INTERLOCK
24 VAC
CLASS 2 CIRCUIT ONLY
HI
MED
LO
NEUTRAL
HI
MED
LO
NEUTRAL
FAN MOTOR 2
(Note 3)
FAN MOTOR 1
DAMPER MOTOR 1
DAMPER MOTOR 2
HI
LO
HI
LO
K5
RELAY
K1
RELAY
K2
RELAY
K3
RELAY
MED
MED
J1-4
J1-6
J1-9
J3-2
J3-1
J1-3
J1-1
J1-8
Door interlock
switch
J1-3 J1-2
120V, 60Hz LINE
120V, 60Hz RETURN
AIR HANDLER
FAN INTERLOCK
24 VAC
CLASS 2 CIRCUIT ONLY
LOGIC DIAGRAM
NOTES
1- CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL
2- FAN MOTOR 2 IS USED ONLY WITH HRVCCLHU1250,
HRVCCLVU1200 AND HRVBBLVU1330
3- DAMPER MOTOR 2 IS USED ONLY WITH HRVCCLVU1200 AND
HRVCCLVU1330
4- IF ANY OF THE ORIGINAL WIRE AS SUPPLIED MUST BE
REPLACED, USE THE SAME OR EQUIVALENT WIRE.
5- FACTORY SET WIRING FOR BLOWER SPEED IS HIGH AND
LOW SPEED. MEDIUM SPEED CAN BE SELECTED INSTEAD OF
LOW SPEED. DISCONNECT RED WIRE FROM MOTOR(S) RED
TAP AND CONNECT TO MOTOR(S) BLUE TAP.
LINE VOLTAGE
CLASS 2 LOW VOLTAGE
AND FIELD WIRING
GAB CD EF
GAB CDEF
RED
FUNCTION TABLE RELAY
MODE K1 K2 K3 K5
Intermittent (20 min per hour) 0 0 0 1
Exchange Low 1 0 1 0
Exchange High 1 1 1 0
Circulation Low 1 0 1 1
Circulation High 1 1 1 1
Defrost Cycle 1 1 1 1
OFF 0 0 0 1
0 = Relay coil is de-energized 1 = Relay coil is energized
Defrost cycles (minutes)
(Defrost / ventilation)
JUMPER TABLE
23
°
F5
°
F -17
°
F
JU1-A JU1-B JU1-C JU1-D JU1-E JU1-F JU1-G MODEL
-5
°
C -15
°
C -27
°
C
OUT OUT OUT OUT IN IN OUT HRVBBSVU1150 6/32 6/32 6/20
OUT OUT OUT OUT IN IN OUT HRVBBSVU1200 6/32 6/32 6/20
OUT OUT OUT OUT IN IN OUT HRVBBLVU1150 6/32 6/32 6/20
OUT OUT OUT OUT IN IN OUT HRVBBLVU1200 6/32 6/32 6/20
OUT OUT OUT OUT IN IN OUT HRVBBLVU1330 6/32 6/32 6/20
OUT OUT OUT OUT IN OUT OUT
Extended defrost all
models
10/30 10/20 10/15
A05224
Fig. 27 --- Wiring Diagram for Models: HRVBBSVU1150, HRVBBSVU1200, HRVBBLVU1150, HRVBBLVU1200, and HRVBBLVU1330

Other manuals for Bryant HRVBBLHA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant HRVBBLHA and is the answer not in the manual?

Bryant HRVBBLHA Specifications

General IconGeneral
BrandBryant
ModelHRVBBLHA
CategoryFan
LanguageEnglish

Related product manuals