EasyManuals Logo

Burkert 5281 Series User Manual

Burkert 5281 Series
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
Type 5281
Fluid Control Systems
Operating instructions
We reserve the right to make technical changes without
notice
Bürkert Werke GmbH Co. All rights reserved
Operating Instructions No. 803 312 01/99/02
BÜRKERT GERMANY
Chr.-Bürkert-Straße 13-17 Berlin Ph: (0 30) 67 97 17 - 0
74653 Ingelfingen Dortmund Ph: (0 23 73) 96 81 - 0
Ph: (0 79 40) 10-0 Dresden Ph: (03 59 52) 36 30 - 0
Fax (0 79 40) 10-204 Frankfurt Ph: (0 61 03) 94 14 - 0
Hannover Ph: (05 11) 9 02 76 - 0
München Ph: (0 89) 82 92 28 - 0
Stuttgart Ph: (07 11) 4 51 10 - 0
BÜRKERT INTERNATIONAL
A Ph. (01) 8 94 13 33 Fax (01) 8 94 13 00
AUS Ph. (02) 96 74 61 66 Fax (02) 96 74 61 67
B Ph. (03) 3 25 89 00 Fax (03) 3 25 61 61
CDN Ph. (9 05) 8 47 55 66 Fax (9 05) 8 47 90 06
CH Ph. (0 41) 7 85 66 66 Fax (0 41) 7 85 66 33
CZ Ph. (06 41) 22 61 80 Fax (06 41) 22 61 81
DK Ph. (0 44) 50 75 00 Fax (0 44) 50 75 75
E Ph. (93) 3 71 08 58 Fax (93) 3 71 77 44
ET Ph. (0 40) 54 27 38 Fax (0 40) 54 41 65
F Ph. (01) 48 10 31 10 Fax (01) 48 91 90 93
GB Ph. (0 14 53) 73 13 53 Fax (0 14 53) 73 13 43
HKG Ph. 24 80 12 02 Fax 24 18 19 45
I Ph. (02) 9 52 01 59 Fax (02) 9 52 90 33
J Ph. (03) 32 47 34 11 Fax (03) 32 47 34 72
KOR Ph. (02) 34 62 55 92 Fax (02) 34 62 55 94
N Ph. (0 63) 84 44 10 Fax (0 63) 84 44 55
MAL Ph. (04) 6 57 66 49 Fax (04) 6 57 21 06
NL Ph. (0 34) 6 59 53 11 Fax (0 34) 6 56 37 17
NZ Ph. (09) 5 70 25 39 Fax (09) 5 70 25 73
P Ph. (01) 4 42 26 08 Fax (01) 4 42 28 08
PL Ph. (0 22) 6 27 47 20 Fax (0 22) 6 27 47 20
RC Ph. (02) 27 58 31 99 Fax (02) 27 58 24 99
S Ph. (0 40) 66 45 100 Fax (08) 7 24 60 22
SF Ph. (09) 5 49 70 600 Fax (09) 5 03 12 75
SGP Ph. 3 83 26 12 Fax 3 83 26 11
TR Ph. (02 32) 4 59 53 95 Fax (02 32) 4 59 76 94
USA Ph. (9 49) 2 23 31 00 Fax (9 49) 2 23 31 98
ZA Ph. (0 11) 3 97 29 00 Fax (0 11) 3 97 44 28
DEAR CUSTOMER
Congratulations on your purchase of this Bürkert appliance. For your
own safety, please carefully read through these operating
instructions before installing the appliance. Your local Bürkert branch
will be pleased to answer any questions you may have.
CIRCUIT FUNCTION
WW A
Type 5281
Coil Kits
Set of
Wearing
Parts Valve
Set of Wearing Parts
Pilot Control
ENGLISH
When planning the application of the device, and during its operation,
observe the general technical rules!
Take suitable measures to prevent unintentional operation or
impermissible impairment!
Note that lines and valves must not be unscrewed from systems that
are under pressure!
Always switch off the voltage supply before working on the system!
If these instructions are ignored, no liability will be accepted from our
side, and the guarantee on the device and on accessories will also
become invalid!
Warning! The surface of the electromagnet can become very hot
during continuous operation. Danger of injury!
To ensure that the device will function correctly, and have a
long service life, please comply with the information in these
Operating Instructions, as well as with the application condi-
tions and permissible data given in the Type 5281 data sheet:
Read the voltage, electrical power, type of protection and
current from the rating plate!
Voltage tolerance: ±10%
Electrical power connection: Instrument socket type 2508 to the tag
connections on the coil (protection class IP 65);
Tightening torque: 1 Nm
When screwing down the instrument socket onto the coil, ensure that
the flat seal is well seated!
With impulse coils, pay attention to asynchronous excitation!
Modular, servo-assisted flow valve with servo-diaphragm and
push-over coil
coil can be locked in 4 x 90° steps, in between which it can be freely
positioned around the armature guide tube
tightening torque of the fixing screws: max. 5 Nm
can be mounted in any position, preferably with the magnetic system
at the top
valve operation A: service port normally closed
media: neutral fluids and gases which do not attack the valve body
and seal or diaphragm materials
seal material: refer to rating plate following the nominal diameter
(NBR, EPDM, FPM)
permissible temperature range of the medium: -10 °C to 100 °C
max. ambient temperature: + 55°
the port connections are compatible with the previous model 281/291
Work on the valve should only be carried out by specialist staff
and with the correct tools!
Clean the piping system before installing the valve!
Where necessary, connect a strainer upstream to protect against
faults!
Pay attention to the flow direction (direction of arrow).
Seal the thread using PTFE tape!
Ensure that there is the full diameter available at the inlets and outlets
to the valve, and that pilot channels are open!
When tightening the pipe connections, never use the valve as a lever!
Be careful of distortion when installing the valve body.
Faults can be caused by soiling, short circuits and loss of power!
Attention: Jammed coils can cause coil overheating with AC!
In case of faults, check the port connections, voltages, type of current
and operational pressure!
Voltage Power Order no.
[V] [W]
024 / DC 8 126 434 R
024 / 56 8 645 556 D
110 / 56 8 645 557 E
230 / 56 8 645 558 P
024 / DC 8 126 434 R
024 / 56 8 645 556 D
120 / 60 8 643 802 B
240 / 60 8 643 803 C
024 / DC 8 126 434 R
024 / 56 8 645 556 D
100 / 56 8 645 559 Q
110 / 56 8 645 557 E
200 / 56 8 645 560 M
230 / 56 8 645 558 P
DN Sealing material Order no.
13 - 65 NBR 645 561 A
13 - 65 FPM 645 562 B
13 - 65 EPDM 645 563 C
13 NBR 624 012 J
13 FPM 624 013 K
13 EPDM 624 014 L
20 NBR 624 015 M
20 FPM 624 016 N
20 EPDM 624 017 P
25 NBR 624 018 Y
25 FPM 624 019 Z
25 EPDM 624 020 W
32, 40 NBR 624 021 K
32, 40 FPM 624 022 L
32, 40 EPDM 624 023 M
50 NBR 624 024 N
50 FPM 624 025 P
50 EPDM 624 026 Q
Valve
SPARE PARTS
Pilot Control
When ordering replacements parts, please also quote the order
number of your complete appliance in addition to the order
number of the replacement parts.
Coil kits Europe
Coil kits A.P.A.C.
Coil kits N.A.F.T.A.
Set of Wearing Parts

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Burkert 5281 Series and is the answer not in the manual?

Burkert 5281 Series Specifications

General IconGeneral
BrandBurkert
Model5281 Series
CategoryControl Unit
LanguageEnglish

Related product manuals