EasyManua.ls Logo

Burkert 8045 - Page 30

Burkert 8045
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
8045
ENGLISH
TEST MENU
0......9
The internal Switch2 must be set in the unlocked position to enter parameters
within this menu. (§ - 3.4.3)
The following parameters can be set within this menu: SECTIONS
4.5.1
4.5.2
4.5.3
4.5.4
ENTER
0......9
4.5 TEST MENU
PRESS SIMULTANEOUSLY FOR 5 SECONDS
OFFSET
SPAN
CALIB 0
FLOW
END
Offset adjustment (4 mA).
Span adjustment (20 mA).
Flow zero-point adjustment.
Entering the flowrate to be simulated. The
outputs will react in accordance to this input.
Return to the operation mode and storage of
the new parameters for CALIB 0, OFFSET
and SPAN. If the OFFSET/SPAN values are
inappropriate the device will revert to
"OFFSET" and new values must be entered.
4.5

Other manuals for Burkert 8045

Related product manuals