TEST MENU
4.5.1 OFFSET ADJUSTMENT
Within this option the user has the possibility of correcting the basic setting of 4 mA
generated by the transmitter. The transmitter generates a value of 4mA by pressing
when"OFFSET" is displayed within the main test menu.
Measure the generated current with an ammeter. If the displayed value is incorrect it
can be corrected by entering the measured value on the ammeter.
Adjustment range: + / - 0.5mA
The corrected value of 4mA is calculated when is pressed when at the END
position within the test menu.
4.5.2 SPAN ADJUSTMENT
Span compensation provides the option of changing the basic setting of 20 mA. The
procedure is identical to that of the offset compensation above. The transmitter
generates 20mA if the key is pressed when "SPAN " is displayed within the
main test menu.
Measure the generated current with an ammeter. If the displayed value is incorrect it
can be corrected by entering the measured value on the ammeter.
Adjustment range: + / - 0.5mA
The corrected value of 20mA is calculated when is pressed when at the END
position within the test menu.
Enter the measured value
Enter the measured value
CALIB 0
4.5.1
ENTER
ENTER
ENTER
ENTER