MAINTENANCE
Faults Status Actions
Is the flow rapidly fluctuating Yes Transmitter not suited ----
for the application
Earth connection
Is the earth connection good
(No noise on the earth line)? No Use a non disturbed earth ----
Are metal pipes connected to the earth? No Connect the pipes to earth ----
Flow measurement incorrect
Correct K-Factor? No Enter the correct 4.4.3
coefficient or determine
via Teach-In
The flow has stopped and the display does
not equal zero Yes Perform a zero point 4.5.3
calibration
Current output value
Switch 1 correctly set? (Sinking or Sourcing) No Select appropriate position 3.4.3
Connection of the current output OK? No Reconnect the current 3.3
output
Fixed current output value
Parameters for current output OK? No Program the current 4.4.4
output
The relays do not work
Parameters OK? No Program the relay outputs 4.4.6
Relays correctly connected? No Connect relays 3.3
Connection of relays 1 and 2 inverted? Yes Connect relays accordingly 3.3
Protection fuses for the relays OK (If any)? No Change the fuses ----
Relay switches ON (if any)? No Switch ON ----