par. description min max def UOM type index R/W notes
loc 7
Field displayed when pressing multifunction once
0 no display 4 Humidity value
1 temperature set point 5 display clock
2 Temperature value 6 enable sleep timer
3 Humidity set point
07
T&H T
- I 21 R/W
46
loc 2
Field displayed when pressing multifunction the second time
0 no display 4 Humidity value
1 temperature set point 5 display clock
2 Temperature value 6 enable sleep timer
3 Humidity set point
07
T&H T
- I 22 R/W
37
loc 11 Value of the password to access the factory parameters 0 999 22 - I 23 R/W
loc 13
Field displayed when pressing multifunction the third time
0 no display 4 Humidity value
1 temperature set point 5 display clock
2 Temperature value 6 enable sleep timer
3 Humidity set point
07
T&H T
- I 24 R/W
60
loc 14
Field displayed when pressing multifunction the fourth time
0 no display 4 Humidity value
1 temperature set point 5 display clock
2 Temperature value 6 enable sleep timer
3 Humidity set point
07
T&H T
- I 25 R/W
70
loc 15
Field displayed when pressing multifunction the  fth time
0 no display 4 Humidity value
1 temperature set point 5 display clock
2 Temperature value 6 enable sleep timer
3 Humidity set point
0 7 0 - I 26 R/W
loc 18 Lock keypad 0 15 0 - I 27 R/W
- Minimum supervisor transmission time 1 60 2 min I 28 R/W
Tab. 5.b
5.3 Sensor variable list
par. description min max def UOM type index R/W notes
- Ambient temperature
T&H T T&H T
-
°C
A
1
R
-20.0 -7.0 80.0 55.0
- Ambient humidity (99.9 T-only model) 1.0 --- 99.9 --- - %rH A 2 R
- Battery level 0.0 100.0 - %rH A 3 R
- Ambient temperature sensor calibration -10.0 10.0 0 °C A 4 R/W
- Ambient humidity sensor calibration -10.0 10.0 0 %rH A 5 R/W
- Minimum temperature variation to force transmission 0.1 5.0 1 °C A 6 R/W
- Minimum humidity variation to force transmission 1.0 10.0 5 %rH A 7 R/W
- Indicative wireless signal level 0.0 -100.0 - Dbm A 8 R
-
Local temperature sensor alarm
0 no temperature sensor alarm
1 temperature sensor alarm
01- D2R
-
Local humidity sensor alarm
0 no humidity sensor alarm
1 humidity sensor alarm
01- D3R
- CAREL address of the device 16 199 - I 4 R
- Minimum supervisor transmission time 1 60 2 Min I 5 R/W
Tab. 5.c
5.4 Repeater variable list
There is no list of supervisor variables for the repeater.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel easy way aria and is the answer not in the manual?

Carel easy way aria Specifications

General IconGeneral
BrandCarel
Modeleasy way aria
CategoryController
LanguageEnglish

Related product manuals