B
brandonwrightSep 4, 2025
What to check if Carel showcase doesn't reach set temperature with valve fully open?
- DDaniel ColemanSep 4, 2025
If a Carel Controller-controlled showcase doesn't reach the set temperature even when the valve is fully open, several issues could be the cause. A blocked solenoid might be preventing proper refrigerant flow, so check that the solenoid opens correctly, inspect the electrical connections, and verify the relay operation. Insufficient refrigerant could also be the problem, so check for air bubbles in the liquid indicator upstream of the expansion valve and ensure the subcooling is suitable (greater than 5 °C); if needed, charge the circuit. Lastly, the valve might be blocked closed, even when commanded open, so use manual control to fully close and open the valve; if the superheat remains high, check the electrical connections and/or replace the valve.