Gas Leakage Detector +0300047IE rel 1.1 - 26.04.2023
Installation
Electrical connection
J1 +
Analogue output
G
Analogue output reference
J2 Sh
Shielded RS485 cable
G0
GND for RS485
A
Tx + / Rx + for RS485
B
Tx- / Rx- for RS485
J3 +24 Vac/dc
For Vac power supply, connect the second transformer wire
+24 Vac/dc
For Vdc power supply, connect one of the two power wires, the device automatically recognises whether this is + or GND.
For Vac power supply, connect one of the two transformer wires.
J4 1A
NO contact for warning/fault relay
2A
Common for warning/fault relay
3A
NC contact for warning/fault relay
J5 1B
NO contact for a alarm relay
2B
Common for alarm relay
3B
NC contact for alarm relay
J6 +
V+ for the output voltage provided for service
G
Service voltage reference
J7 /
Built-in version sensor connector
J8 /
Remote version sensor connector (connection not to be used for built-in products)
7. Secure the detector cover with the four screws.
8. Reposition the previously removed plastic frames.
9. Power the device on and set the parameters using the “RILEVA TE” app (see the relevant chapter) if the settings were not
previously made using the rotary switch.
5. Power the device on and complete the settings using the rotary switch, as described in the following paragraphs, or using
the app, ass described below.
6. Close the cover.
Use the cable glands provided to pass through and connect the cables to the terminals, as shown in the  gure and in the
connection table below. The terminals can be removed to simplify wiring.
J6 J5
3B
2B
1B
3A
2A
1A
+
G
+
B
A
G0
Sh
J4
J3
J2
J1
J7
J8
R1
W3
W2
W1
W8
W7
W6
W5
W4
24 Vac/dc
2.4 Additional installation notes
Before commencing electrical installation and wiring, carefully read the following notes.
Power must be supplied by a safety isolation transformer (Class 2) with no earth connection on the secondary winding.
The cable for the relays must be sized and  tted with fuses based on the rated voltages, currents and environmental condi-
tions.
If stranded wires are used, it is recommended to use an end terminal
To comply with RFI immunity regulations, the communication cable shield on BOSS, mini-BOSS or other supervisors must be
earthed (e.g. to the chassis, earth bar, etc.)
Complete all wiring before powering on.