Gas Leakage Detector +0300047IE rel 1.1 - 26.04.2023
Operation
Soglia
d’allarme
Delay
Valore in ppm
Delay
Soglia di
warning
t
1 2 3 4 5
1 2 3 4 5
300 PreAlarm ag = 0 300 PreAlarm ag = 0 300 PreAlarm ag = 0 300 PreAlarm ag = 1 300 PreAlarm ag = 1
307 PreWarningFlag = 0 307 PreWarningFlag = 1 307 PreWarningFlag = 1 307 PreWarningFlag = 1 307 PreWarningFlag = 1
308 WarningFlag = 0 308 WarningFlag = 0 308 WarningFlag = 1 308 WarningFlag = 1 308 WarningFlag = 1
309 AlarmFlag = 0 309 AlarmFlag = 0 309 AlarmFlag = 0 309 AlarmFlag = 0 309 AlarmFlag = 1
Yellow LED OFF Yellow LED  ashing Yellow LED ON Yellow LED ON Yellow LED ON
Red LED OFF Red LED OFF Red LED OFF Red LED  ashing Red LED ON
Warning relay OFF Warning relay OFF Warning relay ON Warning relay ON Warning relay ON
Alarm relay OFF Alarm relay OFF Alarm relay OFF Alarm relay OFF Alarm relay ON
3.6 Magnetic key for con guration
The device is supplied with a magnet for con guration, located inside one of the two plastic frames on the GLD. By placing it in
the slot provided, the following functions can be managed:
1 2
Bluetooth activation
After 5 seconds of exposing the magnet to the magnetic sensor, Bluetooth mode is activated. If if Bluetooth is already on, after
5 seconds of exposure Bluetooth is deactivated.
Bluetooth mode is automatically deactivated after 20 minutes of inactivity. Product operation in Bluetooth mode is indicated by
the rapid  ashing of the green LED.
Bluetooth Activation set up the product on installation and maintenance operating mode, the alarms if present are disabled,
until the normal operating mode is restored, deactivating bluetooth.
Alarm/warning management
If a warning or alarm is active, after 2 seconds of exposure, the alarm will be acknowledged and deactivated. If gas is still present,
the detector will enter alarm or warning mode as usual, after a 10 minute delay.