+050004104 rel. 2.2 del 26.09.07
10
ENGLISH
H3 Remote control enabling code AD - C 0 255 0
H4 Disable buzzer AD flag C 0 1 0
0: Buzzer enabled
1: Buzzer disabled
H5 Function of relay 5 AD flag C 0 13 1
As for H1
H6 Lock keypad AD - C 0 255 0
H8 Select activation of output with time band AD flag C 0 1 0
0: Time band linked to output configured for light
1: Time band linked to output configured for aux
H9 Enable set point variation with time band AD flag C 0 1 0
0: Set point variation with time band disabled
1: Set point variation with time band enabled
Hdh Anti-sweat heater offset AD °C/°F C -50 200 0.0
Simbol Code Parameter AD U.O.M. Type Min Max Def.
HAn Number of HA events recorded AD - C 0 15 0
HA Date/time of last HA event AD - C - -
y__ Year years 0 99 0
M__ Month months 0 12 1
d__ Day days 0 7 1
h__ Hour hours 0 23 0
n__ Minute minutes 0 59 0
t__ Duration hours 0 99 0
HA1 Date/time of penultimate HA event AD - C - - -
HA2 Date/time of third-to-last HA event AD - C - - -
HFn Number of HF events recorded AD - C 0 15 0
HF Date/time of last HF event AD - C - - -
y__ Year years 0 99 0
M__ Month months 0 12 1
d__ Day days 0 7 1
h__ Hour hours 0 23 0
n__ Minute minutes 0 59 0
t__ Duration hours 0 99 0
HF1 Date/time of penultimate HF event AD - C - - -
HF2 Date/time of third-to-last HF event AD - C 0 - -
Htd HACCP alarm delay AD minutes C 0 250 0
Simbol Code Parameter AD U.O.M. Type Min Max Def.
td1 Defrost time band 1 AD - C - - -
d__ Day days 0 11 0
h__ Hour hours 0 23 0
n__ Minute minutes 0 59 0
td2 Defrost time band 2 AD - C - - -
td3 Defrost time band 3 AD - C - - -
td4 Defrost time band 4 AD - C - - -
td5 Defrost time band 5 AD - C - - -
td6 Defrost time band AD - C - - -
td7 Defrost time band 7 AD - C - - -
td8 Defrost time band 8 AD - C - - -
ton Light/aux on time band, variation set point AD - C - - -
d__ Day days 0 11 0
h__ Hour hours 0 23 0
n__ Minute minutes 0 59 0
toF Light/aux off time band, variation set point AD - C - - -
d__ Day days 0 11 0
h__ Hour hours 0 23 0
n__ Minute minutes 0 59 0
tc RTC date/time setting AD - C - - -
y__ Year years 0 0 99 0
M__ Month months 1 1 12 1
d__ Day of the month days 1 1 31 1
u__ Day of the week hours 6 6 7 1
h__ Hour minutes 0 0 23 0
n__ Minute hours 0 0 59 0
Tab. 4.a
Important warning: for the set times to become immediately operational, turn the instrument on and off again. If the instrument is not switched off, the
times will only become operational when next used, when the internal timers are set.

Other manuals for Carel mastercella

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel mastercella and is the answer not in the manual?

Carel mastercella Specifications

General IconGeneral
SeriesMastercella
Front ProtectionIP65
Protection RatingIP65 (front)
Control TypePID, ON/OFF
DisplayLCD
InputsNTC, PT1000
OutputsRelay, SSR
Storage Temperature-30°C to +70°C
Analogue Outputs4-20 mA, 0-10 V
Serial CommunicationRS485, Modbus RTU
Relative Humidity<90% RH non-condensing