Introduction
1.2.5 Electronic expansion valve driver and Ultracap
The Medium version can control an external driver (EVDmini, EVDice) to drive a unipolar electronic expansion valve, connected
to the Fieldbus serial port (J5 FBus).
See manuals +0300036EN, +0300038EN.
300086_045_R01
EVDM001N00 EVDM011N00 E*VSTA*3** EVDM011S6* EVDMU00R1*
Fig. 1.g
P/NDescription
EVDM000N00 EVD MINI 24V without display
EVDM010N00 EVD MINI 115/230V without display
EVDM011S5* EVD ICE resin bonded 115/230V with Ultracap cable, short version**
EVDM011S6* EVD ICE resin bonded 115/230V with Ultracap cable, long version**
EVDMU00N0* Ultracap module for EVD mini
EVDMU00R1* Ultracap module for EVD ice
(*): 0/1=single/multiple pack (10 pcs.)
(**): valve stator (E2VSTA0330/1) to be ordered separately
Tab. 1.g
1.2.6 Ultracap module
The MPXone Advanced version can provide integrated management of one elec-
tronic expansion valve (CAREL unipolar).
Depending on the application, the Ultracap module and its connection cable need
to be ordered separately; this ensures complete valve closure in the event of a power
failure.
Part number Description
EVD000RAC0 Ultracap module for MPXone Advanced, single pack
ACS00CB002370 Cable kit for Ultracap module, 0.3 m
EVD000RAC0
Fig. 1.h
1.2.7 Transformer
For the panel model.
In relation to the functions used, the following power can be estimated, useful for sizing the transformer:
Application
Standard High e ciency High e ciency with remote display
No. of analogue inputs 5(*) 6(**) 6(**)
No. of analogue outputs - 2 2
No. of external EVD mini/ice drivers - 1 1
No. of remote displays - - 1
Max power consumption (VA) 10 12 15
Tab. 1.h
(*): up to 1 active probe (0-5 V or 4-20 mA);
(**): up to 2 active probes (0-5 V or 4-20 mA).
Part number Description
TRA00AE24(0/1)(*) 230V-24V, 10 VA transformer for panel version
(*)( 0/1): single/multiple pack (10 pcs.)
1.2.8 Unipolar electronic valve
The MPXone Advanced version can provide integrated management of one electronic expansion valve (CAREL unipolar).
The “Z” series of valves is recommended for use with MPXone Advanced.
These in fact guarantee:
High performance in terms of energy effi ciency and reliability
Ability to withstand extreme operating conditions
Simplifi ed logistics management, by reducing the number of part numbers

Related product manuals