Standard Chiller/HP modulare per compressore a vite con driver CAREL
Cod.: +030221241 Rel. 1.0 dated 25 September 03
48
21.4 Short summary of alarms coming from driver
probe error (temperature and/or pressure probe malfunctioning or failed)
stepper motor error (valve motor connections fault)
EEPROM error (EEPROM reading or writing malfunction)
battery error (battery malfunction)
high pressure on EXV driver (operating pressure has exceeded max. MOP threshold)
high pressure on EXV driver (operating pressure has exceeded max. LOP threshold)
superheat low alarm (overheating alarm)
valve not closed during switch-off (valve not fully closed after last blackout)
high intake temperature alarm (operating temperature has exceeded max. threshold)
stand-by for error concerning EEPROM/battery charging or open valve (the system is blocked due to a problems at driver start-up - see the
special "ignore" function)
LAN disconnected (malfunction or fault in 4485 communication between pCO* and driver)