Standard Chiller/HP modulare per compressore a vite con driver CAREL
Cod.: +030221241 Rel. 1.0 dated 25 September 03
50
Type Direction Address Description
D OUT 51 Oil level alarm
D OUT 52 Low pressure alarm from pressure switch
D OUT 53 High pressure alarm from transducer
D OUT 54 Serious alarm from digital input
D OUT 55 Fan 1 thermal cutout alarm
D OUT 56 Fan 2 thermal cutout alarm
D OUT 57 Evaporator pump thermal cutout alarm
D OUT 58 Card 1 offline alarm
D OUT 59 Slave 1 Offline alarm
D OUT 60 Slave 2 Offline alarm
D OUT 61 Slave 3 Offline alarm
D OUT 62 Alarm: Probe 1 failed or not connected
D OUT 63 Alarm: Probe 2 failed or not connected
D OUT 64 Alarm: Probe 3 failed or not connected
D OUT 65 Alarm: Probe 4 failed or not connected
D OUT 66 Alarm: Probe 5 failed or not connected
D OUT 67 Alarm: Probe 6 failed or not connected
D OUT 68 Alarm: Probe 7 failed or not connected
D OUT 69 Alarm: Probe 8 failed or not connected
D OUT 70 Condenser pump duty hours alarm
D OUT 71 Compressor duty hours alarm
D OUT 72 Condenser pump thermal cutout alarm
D OUT 73 Clock alarm
D OUT 74 Phase monitor alarm
D OUT 75 Low pressure alarm from transducer
D OUT 76 High voltage alarm
D OUT 77 High current alarm
D OUT 78 Evaporator pump duty hours alarm
D OUT 79 Values inputting error
D OUT 80 High delivery temperature alarm
D OUT 81 Pressure differential alarm
D OUT 82 Diver 1 probe alarm
D OUT 83 Alarm: driver 1 EEPROM error
D OUT 84 Alarm: driver 1 stepped motor valve error
D OUT 85 Alarm: driver 1 battery error
D OUT 86 Driver 1 high pressure alarm (MOP)
D OUT 87 Driver 1 low pressure alarm (LOP)
D OUT 88 Driver 1 low superheat alarm
D OUT 89 Alarm - valve not shut after driver 1 black-out
D OUT 90 Driver 1 high intake temperature alarm
D OUT 91 Diver 2 probe alarm
D OUT 92 Alarm: driver 2 EEPROM error
D OUT 93 Alarm: driver 2 stepped motor valve error
D OUT 94 Alarm: driver 2 battery error
D OUT 95 Driver 2 high pressure alarm (MOP)
D OUT 96 Driver 2 low pressure alarm (LOP)
D OUT 97 Driver 2 low superheat alarm
D OUT 98 Alarm - valve not shut after driver 2 black-out
D OUT 99 Driver 2 high intake temperature alarm
D OUT 100 Standby due to EEPROM /battery recharge / or open valve error, driver 1
D OUT 101 Standby due to EEPROM /battery recharge / or open valve error, driver 2

Table of Contents

Other manuals for Carel pCO2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel pCO2 and is the answer not in the manual?

Carel pCO2 Specifications

General IconGeneral
BrandCarel
ModelpCO2
CategoryController
LanguageEnglish

Related product manuals