10.2 Características eléctricas del pCO
XS
10.2.1 Entradas analógicas
ADVERTENCIA: para la alimentación de las sondas activas, se puede
utilizar 24 VCC disponibles en el terminal +24 VCC, la corriente
máxima es de 80 mA, protegida contra cortocircuitos.
A diferencia del pCO
B
la señal 0/1 VCC está limitada al rango
restringido de 0-1 V, y por ello no siempre es compatible con la señal
estándar de 10 mV/°C de la sonda CAREL (para temperaturas
negativas y superiores a 100 °C se puede generar alarma de la
sonda), por consiguiente, utilice la 4/20 mA ó NTC).
10.2.2 Entradas digitales
10.2 Electrical specifications pCO
XS
10.2.1 Analogue inputs
WARNING: to supply any active probes, the 24 Vdc available at the
+24 Vdc terminal can be used, the maximum current is 80 mA,
protected against short circuits.
Unlike the pCO
B
, the 0/1 Vdc signal is limited to the restricted range of
0-1 V, and therefore is not always compatible with the standard 10
mV/°C signal from the CAREL probes (for negative temperatures or
temperatures above 100 °C a probe alarm may be generated);
consequently, use the 4/20 mA or NTC for the temperature signals).
10.2.2 Digital inputs
44
pCO
XS
manual - cod. +030220347 - rel. 1.0 - 18.03.03
alimentación (controlador con terminal conectado) 20/60 VCC y 24 VCA ±15% 50/60 Hz - entrada de alimentación máxima en CA P= 8 W,
entrada alimentación máx. en CC P= 6,1 W;
tipo de aislamiento de la alimentación funcional en referencia a la E/S y las conexiones serie
bloque de terminales con conectores macho/hembra extraíbles, tensión máx 250 VCA;
sección del cable min. 0,5 mm
2
- max 2,5 mm
2
;
CPU H8S2320, 16 bit, 24 MHz;
memoria programa (FLASH) 1 MB, a 16 bit (ampliable hasta 2 MB);
memoria de datos (RAM estática) 128 kB a 8 bit (ampliable hasta 512 kB);
memoria de datos de parámetros 4 kB a 16 bit (límite max: 400.000 escrituras por lugar de memoria);
Adicionales 32kB de serie, no disponible para la red pLAN.
Ciclo de funcionamiento (aplicaciones de complejidad media) 0,3 s (típico).
Tabla. 10.2.1
power supply (controller with terminal connected) 20-60 Vdc and 24Vac ±15% 50/60 Hz - maximum power input in ac P= 8W
maximum power input in dc P= 6,1W;
type of power supply insulation functional in reference to the I/O and serial connections
terminal block with removable male/female connectors, max voltage 250Vac;
cable cross-section min. 0.5 mm
2
- max 2.5 mm
2
;
CPU H8S2320, 16 bit, 24 MHz;
program memory (FLASH) 1 MB, at 16 bit (expandable up to 2 MB);
data memory (static RAM) 128 kB at 8 bit (expandable up to 512 kB);
parameter data memory 4 kB at 16 bit (max. limit: 400,000 writes per memory location).
Further 32kB as standard, not available to the pLAN network;
working cycle (applications of average complexity) 0.3 s (typical).
Ta
ble 10.2.1
conversión analógica convertidor 10 bit A/D, con CPU integrada;
tipo B1, B2: sonda de temperatura NTC CAREL (-50T90 °C; R/T 10 k
Ω
a 25 °C), tensión: 0/1 VCC ó 0/5 VCC proporcional,
corriente: 0/20 mA o 4/20 mA, seleccionable mediante software. Resistencia de entrada para 4/20 mA= 100
Ω
;
B3, B4: sonda de temp. NTC CAREL, (-50T90 °C; R/T 10 k
Ω
a 25 °C) ó 0/5 VCC proporcional, seleccionable mediante software;
const. de tiempo de entrada 1 s, para todas las entradas.
Tabla 10.2.1.1
analogue conversion 10 bit A/D converter, with integrated CPU
type B1, B2: CAREL NTC temperature sensor (-50T90 °C; R/T 10 kW at 25 °C), voltage: 0-1 Vdc or 0-5 Vdc ratiometric, current: 0-20 mA
or 4-20mA, selectable via software. Resistance of input for 4-20 mA= 100
Ω
;
B3, B4: CAREL NTC temperature sensor, (-50T90°C; R/T 10 kW at 25 °C) or 0-5Vdc ratiometric, selectable via software;
input time constant 1s, for all the inputs.
Table 9.2.1.1
número de entradas digitales 6
tipo de entradas digitales contacto libre de tensión (alimenta
do por el pCO
XS
)
corriente del contacto 6mA garantizada.
tiempo mínimo de detección de entrada digital NA (abierto-cerrado-abierto) en CA y CC (ms) 150
tiempo mínimo de detección de entrada digital NC (cerrado-abierto-cerrado) en CA y CC (ms) 400
Tabla 9.2.2.1