20 Specications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 18/11/2014
Motor Controllers AC Variable Frequency Drives Type Variex
3
RVLF
Group 01 V/F Pattern selection & setup
No. Description Range
Factory
setting
Unit Note
01-00 Volts/Hz patterns 1~7 1/4 -
01-01 V/F max voltage
200V: 198.0~256.0
400V: 323.0~528.0
220.0/440.0 Vac
01-02 Max frequency 0.20~650.00 50.00/60.00 Hz
01-03 Max frequency voltage ratio 0.0~ 00.0 100.0 %
01-04 Mid frequency 2 0.00~650.00 25.00/30.00 Hz
01-05
Mid frequency voltage ratio 2
0.0~100.0 50.0 %
01-06 Mid frequency 1 0.10~650.00 10.00/12.00 Hz
01-07
Mid frequency voltage ratio 1
0.0~100.0 20.0 %
01-08 Min frequency 0.10~650.00 0.50/0.60 Hz
01-09 Min frequency voltage ratio 0.0~100.0 1.0 %
01-10
Volts/Hz curve modication
(torque boost) V/F start
frequency
0~10.0 0.0 % *1
01-11 V/F start frequency 0.00~10.00 0.0 Hz
Group 02 Motor parameters
No. Description Range
Factory
setting
Unit Note
02-00 Motor no load current ---- A *3
02-01 Motor rated current (OL1) ---- A
02-02
Motor rated slip compensation
0.0~100.0
0.0
% *1
02-03 Motor rated speed ---- Rpm
02-04 Motor rated voltage ---- Vac *4