Specications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network.18/11/2014 21
Motor Controllers AC Variable Frequency Drives Type Variex
3
RVLF
Group 03 Multi function Digital Inputs/Outputs
No. Description Range
Factory
setting
Unit Note
03-00
Multifunction input term. S1 0: Forward/stop command or run/stop
0 -
03-01
Multifunction input term. S2
1: Reverse/stop command or REV/WD 1 -
03-02
Multifunction input term. S3
2: Preset speed 1 (5-02) 2 -
03-03
Multifunction input term. S4
3: Preset speed 2 (5-03) 3 -
03-04
Multifunction input term. S5
4: Preset speed 4 (5-05)
17 -
6: Jog forward command
7: Jog reverse command
8: Up command
9: Down command
10: Acc/dec 2
11: Acc/dec disabled
12: Main/alternative run command select
13: Main/alternative frequency
command select
14: Rapid stop (decel to stop)
15: Base block
16: Disable PID function
17: Reset
18: Auto run mode enable
03-05 Reserved
03-06 Up/Down frequency band 0.00~5.00 0.00 Hz
03-07
Up/Down frequency
modes
0: When up/down is used, the preset
frequency is held as the inverter stops,
and the up/down function is disabled.
0 -
1: When up/down is used, the preset fre-
quency is reset to 0 Hz as the inverter stops.
2: When up/down is used, the preset
frequency is held as the inverter stops,
and the up/down is available.
03-08 S1~S5 scan conrmation 1~400. Number of scan cycles 20 1ms
03-09 S1~S5 switch type select
xxxx0: S1 NO xxxx1: S1 NC
00000 -
xxx0x: S2 NO xxx1x: S2 NC
xx0xx: S3 NO xx1xx: S3 NC
x0xxx: S4 NO x1xxx: S4 NC
0xxxx: S5 NO 1xxxx: S5 NC
03-10 Reserved
03-11 Output relay (RY1)
0: Run
0 -
1: Fault
2: Setting frequency reached
3: Frequency reached (3-13±3-14)
4: Output frequency detection 1 (> 3-13)
5: Output frequency detection 2 (< 3-13)
6: Auto-Restart
7: Momentary AC power loss
8: Rapid stop
9: Base block
10: Motor overload protection (OL1)
11: Drive overload protection (OL2)
12: Reserved
13: Output current reached
14: Brake control