Motor Controllers AC Variable Frequency Drives Type Variex
3
RVLF
“NO” indicates normally open, “NC” indicates normally closed.
Group 03 Multi function digital Inputs/Outputs
No. Description Range
Factory
setting
Unit Note
03-12
Reserved
03-13 Output frequency detection level (Hz) 0.00~650.00 0.00 Hz *1
03-14 Frequency detection band 0.00~30.00 2.00 Hz *1
03-15 Output current detection level 0.1~15.0 0.1 A
03-16 Output current detection period 0.1~10.0 0.1 sec
03-17 External brake release level 0.00~20.00 0.00 Hz
03-18 External brake engage level 0.00~20.00 0.00 Hz
03-19 Relay output function type
0: A (Normally open)
1: B (Normally close)
0 -
Group 04 Analog signal inputs/Analogue output functions
No. Description Range
Factory
setting
Unit Note
04-00
AVI/ACI analog input signal type
select
AVI ACI
0 -
0:0~10V 0~20mA
1:0~10V 4~20mA
2:2~10V 0~20mA
3:2~10V 4~20mA
04-01 AVI Signal verication scan rate 1~400 100 1ms
04-02 AVI Gain 0~1000 100 % *1
04-03 AVI Bias 0~100 0 % *1
04-04 AVI Bias selection 0: Positive 1: Negative 0 - *1
04-05 AVI Slope 0: Positive 1: Negative 0 - *1
04-06 ACI Signal verication scan rate 1~400 100 1ms
04-07 ACI Gain 0~1000 100 % *1
04-08 ACI Bias 0~100 0 % *1
04-09 ACI Bias selection 0: Positive 1: Negative 0 - *1
04-10 ACI Slope 0: Positive 1: Negative 0 - *1
04-11 Analog output mode (AO)
0: Output frequency
1: Frequency command
2: Output voltage
3: DC Bus voltage
4: Motor current
0 - *1
04-12 Analog output AO gain (%) 0~1000 100 % *1
04-13 Analog output AO bias (%) 0~1000 0 % *1
04-14 AO Bias selection
0: Positive
1: Negative
0 - *1
04-15 AO Slope
0: Positive
1: Negative
0 - *1