5.5 - Shipping
Follow the handling instructions affixed to the packages
Do not stand on the packages
Do not place anything on top of the packages
Strap the packages onto the deck of the truck
Only textile straps are authorised (lifting and coupling)
Use an open top for container shipping single-line machines, but use the option intended for this purpose for other machines.
6 - STORAGE
Store the units at a temperature of between -40 and +60°C (temperature range for standard units). For options, see the relevant
description.
Protect the units against impacts and ensure that they only support their own weight.
Place the units on firm, flat and level ground. For storage in very windy areas, affix the unit to the ground using straps or cables.
Leave the blanking trim for the pipes in place before connecting the unit.
For long-term storage (over 3 months), fill the exchanger with an inert gas and seal the pipes using caps. This is necessary to
prevent the formation of condensation and oxidation. Warning: do not exceed the maximum operating pressure indicated on the
data plate.
For long-term storage, it is recommended to place the units in an area protected from adverse weather conditions.
7 - INSTALLATION
Contact us for projects with a "special" seismic risk.
Before setting up the unit in its intended location, the installer must check the following points:
- The unit must be installed outdoors in an area protected from flooding. Ensure that all conditions have been taken into account
(negative outdoor temperatures, corrosive atmosphere, altitude, etc.)
- The ground surface or structure must be level and strong enough to bear the unit's weight.
- Raise the unit if it is installed in a snowy area, in order to ensure a sufficient air intake height.
- At the design stage, check that the installation location is compatible with the unit's sound level.
- For vertical units, the flow of air crossing the unit must not be parallel to the prevailing wind.
- Protect the unit from sandstorms using the appropriate infrastructure.
- Waste from vegetation is a major factor contributing to the clogging of the coil; avoid installing the unit close to deciduous trees.
- Do not install the unit near hot air extraction duct outlets.
7.1 - Maximum permitted wind speed
Maximum permitted speed: 100 Km/h.
For speeds > 100 Km/h, contact us.
5 - INSTRUCTIONS FOR LIFTING AND PLACING THE FEET IN THE OPERATING
POSITION AND FOR SHIPPING
8