Fig. 6 — Typical Pumpout Unit/Chiller Connection Schematic
1-1/4 in. NPT
1-1/4 in. NPT
CHILLERS WITHOUT ISOLATION VALVES
CHILLERS WITH ISOLATION VALVES
(WITH OR WITHOUT PUMPOUT STORAGE TANKS)
GENERAL PIPING CONNECTION SIZES
NOTES:
1. The field-supplied tubing is to be 1/2-in. OD tubing (min.) and
must be arranged and supported to avoid stresses on the equip-
ment, transmission of vibrations, and interference with routine
access during the reading, adjusting, and servicing of the equip-
ment. If the distance from the chiller to the pumpout unit is over
50 ft, then 7/8-in. OD tubing (min.) must be used. Provisions
should be made for adjustment in each plane of the tubing and
for both periodic and major servicing of the equipment. Special
care must be taken so that the safety head does not experience
tubing strain. Vent the safety head per ASHRAE 15 (American
Society of Heating, Refrigerating, and Air-Conditioning Engi-
neers), latest revision.
2. The tubing and valve from the storage tank to the pumpout com-
pressor is factory supplied when the unit is factory mounted.
CONNECTION SIZE (in.)
Refrigerant Transfer Connections 1/2 Flare (male)
Condenser Water Cooling Connectors 3/4 NPT (female)
Safety Relief Head Pumpdown 3/8 Flare (male)
LEGEND
Factory-Supplied Tubing
Field-Supplied Tubing
Field-Supplied Tubing (Multiple Chillers)
Service Valve (Factory Supplied)
Service Valve (Field Supplied)
a19-1575ef
a19-1576ef