19XR PIC II ISM_CONF TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Starter Type
(0=Full, 1=Red, 2=SS/VFD)
0to2 1
Motor Rated Line Voltage 200 to 13200 VOLTS 460
Volt Transformer Ratio: 1 1to33 1
Overvoltage Threshold 105 to 115 % 115
Undervoltage Threshold 85 to 95 % 85
Over/Under Volt Time 1to10 SEC 5
Voltage % Imbalance 1to10 % 5
Voltage Imbalance Time 1to10 SEC 5
Motor Rated Load Amps 10 to 5000 AMPS 200
Motor Locked Rotor Trip 100 to 60000 AMPS 1000
Locked Rotor Start Delay 1 to 10 cycles 5
Starter LRA Rating 100 to 60000 AMPS 2000
Motor Current CT Ratio: 1 10 to 1000 100
Current % Imbalance 5to40 % 15
Current Imbalance Time 1to10 SEC 5
3 Grnd Fault CT’s? (1=No) 0/1 NO/YES YES
Ground Fault CT Ratio: 1 150 150
Ground Fault Current 1 to 25 AMPS 15
Ground Fault Start Delay 1 to 20 cycles 10
Ground Fault Persistence 1 to 10 cycles 5
Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE
Frequency-60 Hz? (No=50) 0/1 NO/YES YES
Line Frequency Faulting 0/1 DSABLE/ENABLE DSABLE