19XR PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
0/1 0
Min. Load Point (T1/P1)
Surge/HGBP Delta T1 0.5 to 15 ^F 1.5
Surge/HGBP Delta P1 30 to 170 PSI 50
Full Load Point (T2/P2)
Surge/HGBP Delta T2 0.5 to 15 ^F 10
Surge/HGBP Delta P2 50 to 170 PSI 85
Surge/HGBP Deadband 0.5 to 3 ^F 1
Surge Protection
Surge Delta % Amps 5to15 % 10
Surge Time Period 7to10 MIN 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE DSABLE
Ice Build Termination
0=Temp, 1=Contacts,2=Both
0to2
0
Ice Build Recycle 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Alarm mA 4to20 mA 20
CL-6