19XR PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Comp Motor Temp Override 150 to 200 DEG F 200
Cond Press Override 90 to 165 PSI 125
Comp Discharge Alert 125 to 200 DEG F 200
Comp Thrust Brg Alert 165 to 185 DEG F 175
Chilled Medium 0/1 WATER/BRINE WATER
Chilled Water Deadband .5 to 2.0 ^F 1.0
Evap Refrig Trippoint 0.0 to 40.0 DEG F 33
Refrig Override Delta T 2.0 to 5.0 ^F 3
Condenser Freeze Point −20 to 35 DEG F 34
Evap Flow Delta P Cutout 0.5 to 50.0 PSI 5.0
Cond Flow Delta P Cutout 0.5 to 50.0 PSI 5.0
Water Flow Verify Time 0.5 to 5 MIN 5
Oil Press Verify Time 15 to 300 SEC 40
Recycle Control
Recycle Restart Delta T 2.0 to 10.0 DEG F 5
Recycle Shutdown Delta 0.t to 4.0 DEG F 1
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable 0to4 0
Spare Temp #1 Limit −40 to 245 DEG F 245
Spare Temp #2 Enable 0to4 0
Spare Temp #2 Limit −40 to 245 DEG F 245