19XR PIC II SETUP2 TABLE CONFIGURATION SHEET
DESCRIPTION STATUS UNITS DEFAULT VALUE
Capacity Control
Proportional Inc Band 2to10 6.5
Proportional Dec Band 2to10 6.0
Proportional ECW Gain 1to3 2.0
Guide Vane Travel Limit 30 to 100 % 80
Diffuser Control
Diffuser Option 0 to 1 DSABLE/ENABLE DSABLE
Guide Vane 25% Load Pt 0to78 % 25
Diffuser 25% Load Pt 0to100 % 0
Guide Vane 50% Load Pt 0to78 % 50
Diffuser 50% Load Pt 0to100 % 0
Guide Vane 75% Load Pt 0to78 % 75
Diffuser 75% Load Pt 0to100 % 0
Diffuser Full Span mA 15 to 22 mA 18
VFD Speed Control
VFD Option 0/1 DSABLE/ENABLE DSABLE
VFD Gain 0.1 to 1.5 0.75
VFD Increase Step 1to5 % 2
VFD Minimum Speed 65 to 100 % 70
VFD Maximum Speed 90 to 110 % 100