General information
The nominal ow rate of the installation will be set using a manual 
valve that should be installed on the leaving water piping (item
18).
Due to the pressure drop it generates on the hydraulic network,
this ow control valve is used to set the network pressure/ow rate 
curve to the pump pressure/ow rate curve, to obtain the nominal 
ow rate at the desired operation point.
This will be checked using the reading for the pressure drop in
the unit (evaporator).
As the exact total installation pressure drop is not known prior to
commissioning, it is necessary to adjust the water ow rate with 
the control valve (item 18) to obtain the installation's specic ow 
rate.
Hydraulic circuit cleaning procedure
Open all control valves completely (item 18).
Start up the system pump.
Read the evaporator pressure drop as the di󰀨erence on the 
pressure gauge connected to the unit inlet then the outlet (item
16).
Let the pump run for 2 hours continuously to ush the system's 
hydraulic circuit (presence of contaminating solids).
Perform another reading.
Compare this value to the initial value.
An  increasing  Delta  P  value  indicates  that  the  lters  on  the 
installation needs to be removed and cleaned. In this case, close
the shut-o󰀨 valves on the water inlet and outlet (item 19). Remove 
then clean the lters (item 1) after draining the hydraulic part of 
the unit (item 9).
Purge the air from the circuit (item 10).
Repeat until all fouling is removed from the lter.
Water ow rate adjustment procedure
Once the circuit is cleaned, read the pressures on the pressure
gauges (water inlet and outlet pressure) to determine the pressure
drop at the evaporator terminals. Compare the value obtained with
the design value predicted by the selection software.
If  the  pressure  drop  reading  is  above  the  specied  value,  this 
indicates that the ow rate at the terminals of the unit (and therefore 
within the system) is too high. In this case, close the control valve
(item  18)  and  read  the  new  pressure  di󰀨erence.  Repeat  as 
necessary,  closing  the  control  valve  until  the  specic  pressure 
drop corresponding to the unit's nominal ow rate at the design 
point is achieved.
NOTE: If the network has an excessive pressure drop in
relation to the available static pressure delivered by the
system pump, the nominal water ow cannot be obtained
(lower resulting flow) and the difference in temperature
between the water inlet and outlet of the evaporator will be
increased.
To reduce the hydraulic system pressure drop:
Reduce the pressure drops of individual components (elbows,
level changes, options, etc.) as much as possible,
Use the correct pipe diameter,
Do not extend the hydraulic systems.
4.7 - Evaporator water ow recirculation
If the installation ow rate is less than the minimum unit ow rate, 
the evaporator ow can be recirculated, as shown in the diagram.
For minimum chilled water ow rate
B
C
Legend:
B
Evaporator
C
Recirculation
4 - WATER CONNECTIONS