9.3 - Essential points to check
9.3.1 - Compressors
Ensure that each compressor is rotating in the correct direction,
by checking that the discharge temperature rises quickly, the HP
increases and the LP drops. If it is rotating in the wrong direction,
the electric power supply is incorrectly wired (reversed phases).
To ensure rotation in the correct direction, swap two power supply
phases.
Check the compressor discharge temperature with a contact
sensor
Check the input current; it should be normal
Check all safety devices to make sure they operate correctly
9.3.2 - Hydraulics
As the exact total system pressure drop is not known at
commissioning, adjust the ow of water with the control valve until 
the desired nominal rate is obtained.
By modifying the pressure drop in the hydraulic network, the control
valve aligns the system pressure/ow curve with that of the pump 
so that the nominal ow rate corresponding to the desired operating 
point is obtained. The pressure drop in the water exchanger (read
using the pressure gauge placed on the exchanger inlet and outlet)
is the reference to be used to check and adjust the nominal ow 
rate of the system.
Follow the procedure described below:
Open the control valve completely
Let the pump run for two hours to ush out any solid particles 
in the circuit
Read the pressure drop in the water exchanger when the pump
is turned on and then two hours afterwards
If the pressure drop has decreased, this means that the screen
lter is clogged. It must be removed and cleaned
Repeat until the lter is completely clean
If the system pressure drops are above the available static
pressure delivered by the pump, the resulting water ow rate 
will  be  low  and  the  di󰀨erence  in  temperature  between  the 
exchanger inlet and outlet will be too high. This is why pressure
drops must be minimised. Check that this di󰀨erence is within 
the values on the curve (refer to the section "Water type heat 
exchanger min. water volume and ow rate")
9.3.3 - Refrigerant charge
Each unit is shipped with an exact charge of refrigerant (see the
table of physical properties).
Check that there are no visible refrigerant or oil leaks :
No  apparent  damage  on  the  refrigerant  circuit  pipes
(no trauma, cracks, deformation)
No traces of grease on the connections and refrigerant circuit 
sensors.
In case of doubt, use a refrigerant leak detection device suited to
the uid in the unit.
9.3.4 - Ventilation for electrical cabinets
Check that the air ows from the cooling fans are directed from 
the outside of the cabinets to the inside (ensuring fresh air is drawn
towards the inside).