5.11 - Electrical data
5.11.1 - Electrical data of standard units
5.11.1.1 - 30KAV-ZE
Units 350 - 1300 kW
30KAV-ZE 350A 400A 450A 500A 550A 600A 650A 750A 800A 900A 1000A 1100A 1200A 1300A
Power circuit supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power
(1)
Standard unit kW 176 192 214 232 252 288 316 353 380 418 459 499 550 608
Power factor at maximum power
(1) (2)
0,91-0,93
Displacement Power Factor (Cos Phi) >0,98
Total harmonic distortion (THDi)
(1) (3)
% 35-45%
Maximum operating current draw (Un)
(1)
Standard unit A 274 298 333 361 391 447 491 549 591 649 713 775 854 945
Maximum operating current draw (Un-10%)
(1)
Standard unit A 299 325 363 384 416 484 522 585 629 709 778 825 919 1006
Start-up current
(4)
Standard unit A 175 186 203 217 232 300 327 320 340 399 430 461 535 544
(1) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(2) The value decreases as the input power is reduced
(3) May vary depending on the short-circuit ratio of the installation.
The THDi value increases as the input power drops. However, the eects on the installation are greater when the current is at its maximum. For this reason,
the installation's compliance with standards relating to voltage harmonics (for example, the IEC standard 60000-2-4) must usually be checked at the maximum load
condition, to ensure the other operating scenarios are covered.
(4) Operating current of the biggest compressor + fan current + starting current of the smallest compressor.
Starting current values used for the compressor are : 06ZCE1-H3AA06013 = 40A ; 06ZFC2-3AA06013 = 50A ; 06ZJG3-3AA06013 = 80A.
5.11.1.2 - 30KAVIZE
Units 500 - 1250 kW
30KAVIZE 500 800 1100 1250
Power circuit supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power
(1)
Standard unit kW 261 405 520 626
Power factor at maximum power
(1) (2)
0,91-0,93
Displacement Power Factor (Cos Phi) >0,98
Total harmonic distortion (THDi)
(1) (3)
% 35-45
Maximum unit current draw (Un)
(1)
Standard unit A 405 628 808 973
Maximum unit current draw (Un-10%)
(1)
Standard unit A 430 668 860 1038
Start-up current
(4)
Standard unit A 239 249 477 558
(1) Values obtained at operation with maximum operating power input (data given on the unit nameplate)
(2) Value decreases when load lowers
(3) May vary according to the installation’s short circuit ratio
THDi increases when load lowers. But the highest impact on the installation occurs when the current is maximum. Therefore compliance of the installation regarding
voltage harmonic distortion at PCC (per IEC61000-2-4 or other standard) shall be usually checked at max load in order to cover all load conditions.
(4) Operating current of the biggest compressor + fan current + starting current of the smallest compressor.
Starting current values used for the compressor are : 06ZCE1-H3AA06013 = 40A ; 06ZFC2-3AA06013 = 50A ; 06ZJG3-3AA06013 = 80A.