8 - PHYSICAL DATA
8.1 - Physical data
8.1.1 - Physical data of standard units
8.1.1.1 - Units 30KAV-ZE 350 kW - 800 kW
30KAV-ZE 350A 400A 450A 500A 550A 600A 650A 750A 800A
Sound levels
Standard unit
Sound power
(1)
dB(A) 95 95 96 98 99 98 99 98 100
Sound pressure at 10 m
(2)
dB(A) 63 63 64 65 66 65 67 65 67
Sound pressure level at 1 m dB(A) 75 75 76 78 78 77 78 77 78
Dimensions
Standard unit
Length mm 4387 4387 5578 5578 6772 6772 7962 7962 9155
Width mm 2261 2261 2261 2261 2261 2261 2261 2261 2261
Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324
Operating weight
(4)
Standard unit kg 4691 4700 5067 5077 5519 5951 6367 6813 7199
Compressors
Standard unit
06Z twin screw variable speed with AC induction motor and variable frequency 
drive
Unit + option 329
(3)(6)
06Z twin screw variable speed with AC permanent magnet motor and variable 
frequency drive
Circuit A Quantity 1 1 1 1 1 1 1 1 1
Circuit B Quantity 1 1 1 1 1 1 1 1 1
Unit minimum part load
(5)
% 13 13 13 13 13 13 13 12 12
Refrigerant
(4)
R1234ze A2L (GWP=1 following AR5, ODP=0)
Circuit A
kg 49 47 53 56 64 77 86 81 87
tCO
2
e 0,34 0,33 0,37 0,39 0,45 0,54 0,60 0,57 0,61
Circuit B
kg 50 48 54 57 65 58 68 82 88
tCO
2
e 0,35 0,34 0,38 0,40 0,46 0,41 0,48 0,57 0,62
Oil Oil for R1234ze. Contact Carrier ERCD for supplying.
Circuit A l 27 26 25 23 20 23 20 23 20
Circuit B l 27 26 25 23 20 23 20 23 20
Unit control SmartVu™ interface with 7" colour touch screen
Languages
 10 languages (DE, EN, ES, FR, IT, NL, PT, TR, TU + one chosen  
by the customer)
Smart energy metering Standard feature
Wireless connectivity Option
Expansion valve Electronic expansion valve
Air heat exchanger Novation™ micro-channel heat exchanger
Fans 
Standard unit
Flying Bird™ VI impeller variable speed with AC motor and variable frequency 
drive
Unit + option 17
(3)
Flying Bird™ VI impeller variable speed with EC motor
Quantity 6 6 8 8 10 10 12 12 14
Maximum total air ow l/s 35580 35580 47440 47440 59300 59300 71160 71160 83020
Maximum rotation speed r/s 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0 16,0
Water heat exchanger Flooded shell and tube heat exchanger
Water volume l 83 88 96 100 115 126 144 165 183
Max. water-side operating pressure without hydraulic 
module
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000
Water connections Victaulic
®
 type
Standard unit
Connections  inch 5 5 6 6 6 6 8 8 8
Outside tube diameter mm 141,3 141,3 168,3 168,3 168,3 168,3 219,1 219,1 219,1
Casing paint Colour code RAL 7035
(1)  In dB ref=10
-12
 W, 'A' weighted. Declared noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in accordance with  
ISO 9614-1 and certied by Eurovent.
(2)  In dB ref 20µPa, 'A' weighted. Declared noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information, calculated from the sound 
power Lw(A).
(3)  Options: 15=Low noise level ; 15LS=Very low noise level ; 17=Fans motors EC type ; 329=Compressors motors PM type
(4)  Values are guidelines only. Refer to the unit name plate.
(5)  For standard conditions. Depending on operating conditions, unit might have a dierent minimum part load or cycle.
(6)  Option 329 is not available on units 0900 to 1300.
Eurovent certied values
46