30KAV-ZE + option 119 0900A 1000A 1100A 1200A 1300A
Power circuit supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power
(1)
Unit + option 119 kW 408 447 480 - -
Unit + option 119 + option 17 kW 403 442 475 - -
Unit + option 329 kW - - - - -
Unit + option 329 + option 119 kW - - - - -
Power factor at maximum power
(1)(2)
0,91-0,93
Displacement Power Factor (Cos Phi) >0,98
Total harmonic distortion (THDi)
(1)(3)
% 35-45%
Maximum operating current draw (Un)
(1)
Unit + option 119 A 634 694 746 - -
Unit + option 119 + option 17 A 627 687 738 - -
Unit + option 329 A - - - - -
Unit + option 329 + option 119 A - - - - -
Maximum operating current draw (Un-10%)
(1)
Unit + option 119 A 691 756 794 - -
Unit + option 119 + option 17 A 684 749 786 - -
Unit + option 329 A - - - - -
Unit + option 329 + option 119 A - - - - -
Start-up current
(4)
Unit + option 119 A 391 420 446 - -
Unit + option 119 + option 17 A 388 417 442 - -
Unit + option 329 A - - - - -
(1) Values obtained at operation with maximum operating power input (data given on the unit nameplate)
(2) Value decreases when load lowers
(3) May vary according to the installation’s short circuit ratio
THDi increases when load lowers. But the highest impact on the installation occurs when the current is maximum. Therefore compliance of the installation regarding
voltage harmonic distortion at PCC (per IEC61000-2-4 or other standard) shall be usually checked at max load in order to cover all load conditions.
(4) Operating current of the biggest compressor + fan current + starting current of the smallest compressor.
Starting current values used for the compressor are : 06ZCE1-H3AA06013 = 40A ; 06ZFC2-3AA06013 = 50A ; 06ZJG3-3AA06013 = 80A.
5.11.2.1 - Units 30KAVPZE
30KAVPZE 350A 400A 450A 500A 550A 600A 650A 750A 800A
Power circuit supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power
(1)
Standard unit kW 172 192 196 213 237 271 295 332 353
Power factor at maximum power
(1) (2)
0,91-0,93
Displacement Power Factor (Cos Phi) >0,98
Total harmonic distortion (THDi)
(1) (3)
% 35-45%
Maximum operating current draw(Un)
(1)
Standard unit A 268 298 306 332 368 421 459 516 550
Maximum operating current draw (Un-10%)
(1)
Standard unit A 291 317 334 354 392 456 488 550 586
Start-up current
(4)
Standard unit A 173 188 193 206 228 287 320 306 334
(1) Values obtained at operation with maximum operating power input (data given on the unit nameplate)
(2) Value decreases when load lowers
(3) May vary according to the installation’s short circuit ratio
THDi increases when load lowers. But the highest impact on the installation occurs when the current is maximum. Therefore compliance of the installation regarding
voltage harmonic distortion at PCC (per IEC61000-2-4 or other standard) shall be usually checked at max load in order to cover all load conditions.
(4) Operating current of the biggest compressor + fan current + starting current of the smallest compressor.
Starting current values used for the compressor are : 06ZCE1-H3AA06013 = 40A ; 06ZFC2-3AA06013 = 50A ; 06ZJG3-3AA06013 = 80A.