8.1.1.3 - Units 30KAVIZE
Units 500 - 1250 kW
30KAVIZE 500 800 1100 1250
Sound levels
Standard unit
Sound power
(1)
dB(A) 102 103 101 105
Sound pressure at 10 m
(2)
dB(A) 70 70 68 72
Sound pressure level at 1 m dB(A) 82 82 79 83
Dimensions
Standard unit
Length mm 4350 6735 9157 9157
Width mm 2261 2261 2261 2261
Height mm 2324 2324 2324 2324
Operating weight
(4)
Standard unit kg 4877 6679 9143 9266
Compressors
Standard unit
06Z twin screw variable speed with AC induction motor and variable
frequency drive
Unit + option 329
(3)(6)
06Z twin screw variable speed with AC permanent magnet motor and
variable frequency drive
Circuit A Quantity 1 1 1 1
Circuit B Quantity 1 1 1 1
Unit minimum part load
(5)
% 13 12 13 10
Refrigerant
(4)
R1234ze A2L (GWP=1 following AR5, ODP=0)
Circuit A
kg 54 80 114 118
tCO
2
e 0,38 0,56 0,80 0,83
Circuit B
kg 55 81 112 116
tCO
2
e 0,39 0,57 0,78 0,81
Oil Oil for R1234ze. Contact Carrier ERCD for supplying.
Circuit A l 20 20 30 30
Circuit B l 20 20 30 30
Unit control SmartVu™ with 7 inch coloured touch screen interface
Languages
 10 languages (DE, EN, ES, FR, IT, NL, PT, TR, TU + one on customer 
choice)
Smart energy metering Standard feature
Wireless connectivity Option
Expansion valve Electronic expansion valve
Air heat exchanger Novation™ Micro Channel Heat Exchanger
Fans
Standard unit
Flying Bird™ VI impeller variable speed with AC motor and variable
frequency drive
Unit + option 17
(3)
Flying Bird™ VI impeller variable speed with EC motor
Quantity 6 10 14 14
Maximum total air ow l/s 35580 59300 83020 83020
Maximum rotation speed r/s 16,0 16,0 16,0 16,0
Water heat exchanger Flooded shell and tube heat exchanger
Water volume l 115 183 243 270
Max. water-side operating pressure without hydraulic module kPa 1000 1000 1000 1000
Water connections Victaulic
®
type
Standard unit
Connections inch 6 8 8 8
Outside tube diameter mm 168,3 219,1 219,1 219,1
Casing paint Colour code RAL 7035
(1) in dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certied by Eurovent.
(2)  In dB ref 20μPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, 
calculated from the sound power Lw(A).
(3) Options: 15=Low noise level ; 15LS=Very low noise level ; 17=Fans motors EC type ; 329=Compressors motors PM type
(4) Values are guidelines only. Refer to the unit name plate.
(5)  For standard conditions. Depending on operating conditions, unit might have a di󰀨erent minimum part load or cycle.
Eurovent certied values
8 - PHYSICAL DATA