High pressure dual pump motors (option 116W)
No.
(2)
Description
(3)
350A 400A 450A 500A 550A 600A
1
Nominal e󰀩ciency at full load and nominal voltage % 90,3 91,3 91,3 91,3 91,9 91,9
Nominal e󰀩ciency at 75% of full load and nominal voltage % 90,3 91,4 91,4 91,4 92,1 92,1
Nominal e󰀩ciency at 50% of full load and nominal voltage % 88,9 90,3 90,3 90,3 90,4 90,4
2 E󰀩ciency level - IE3
3 Year of manufacture -
This information varies depending on the manufacturer
and model at the time of incorporation. Please refer to
the motor nameplates.
4
Manufacturer's name and trademark, commercial registration number
and place of manufacturer
- Same as above
5 Product's model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 7,5 11 11 11 15 15
7-2 Maximum input power (400 V)
(4)
kW 8,31 12,05 12,05 12,05 16,38 16,38
8 Nominal input frequency  Hz 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)
(5)
A 13,20 18,70 18,70 18,70 25,20 25,20
10 Nominal speed
r/s -
rpm
48,9
- 2935
49,1
- 2945
49,1
- 2945
49,1
- 2945
49,1
- 2945
49,1
- 2945
11 Product disassembly, recycling or disposal at end of life -
Disassembly using standard tools. Disposal and
recycling using an appropriate company.
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C
Please refer to the operating conditions given
in this manual or in the specic conditions in 
the Carrier selection programs.
IV - Potentially explosive atmospheres - Non-ATEX environment
(1)  Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2)  Item number imposed by regulation No. 640/2009, annex I2b.
(3)  Description given by regulation No. 640/2009, annex I2b.
(4)  To obtain the maximum input power for a unit with hydraulic module, add the "maximum operating input power" for the unit (see Electrical data table) to the pump power.
(5)  To obtain the maximum unit operating current draw for a unit with hydraulic module add the "maximum unit operating current draw" (Electrical data table) to the pump 
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.