Record Configuration Information
MODE -- CONFIGURATION
SUB-MODE ITEM ITEM EXPANSION
DISP TEST Test Display LED's
METR Metric Display
LANG Language
UNIT TYPE Unit Type
TONS Unit Size
VAR.A NB Fans on Varifan Cir A
SERV
VAR.B NB Fans on Varifan Cir B
VAR.C NB Fans on Varifan Cir C
VOLT Power Supply Voltage
60HZ 60HZ frequency
STAR Soft Starter Select
Y.D Wye Delta Start Select
MTA.A Must Trip Amps cir A
R.MT.A Read Must Trip Amps A
MTA.B Must Trip Amps cir B
R.MT.B Read Must Trip Amps B
MTA.C Must Trip Amps cir C
RMT.C Read Must Trip Amps C
C.SW.A $1 Config switch cir A
R.CS.A Read $1 Config switch A
C.SW.B $1 Config switch cir B
R.CS.B Read $1 Config switch B
C.SW.C $1 Config switch cir C
R.CS.C Read $1 Config switch C
RECL Heat Reclaim Select
EHS Electrical Heater Stage
EMM EMM module installed
PAS.E Password Enable
PASS Factory Password
CO.HT Cooler Heater Select
CON.V Condenser Valve Select
FREE Free cooling Select
HGBP Hot Gas Bypass Select
MCHX MCHX Exchanger Select
HI.TI High Tiers display Selec
FLUD Cooler Fluid Type
CFLU Condenser Fluid Type
MOP EXV MOP Setpoint
HRTH High Pressure Threshold
SHRA Cir A Superheat Setp
SHRB Cir B Superheat Setp
SHRC Cir C Superheat Setp
HTR Cooler Heater DT Setp
EWTO Entering water control
AU.SM Auto Start when SM lost
LOSP Brine Freeze Setpoint
FL.SP Brine Flow Switch Setp
HD.PG Varifan Proportion Gain
HD.DG Varifan Derivative Gain
HD.IG Varifan Integral Gain
HR.MI Reclaim Water Valve Min
HR.MA Reclaim Water Valve Max
DISPLAY
ON/OFF
US-METR
X
X
XXX
0-6
0-6
0-6
XXX
NO-YES
NO-YES
NO-YES
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
NO-YES
0-4
NO-YES
ENBL/DSBL
XXX
NO-YES
NO-YES
NO-YES
NO-YES
NO-YES
NO-YES
WATER-BRINE
WATER-BRINE
XX.X
XXX.X
XX.X
XX.X
XX.X
XX.X
NO-YES
NO-YES
XX.X
XX.X
XX.X
XX.X
XX.X
XXX.X
XXX.X
DEFAULT
OFF
US
English
Air-Cooled
0: No low ambient
temperature head
)ressure control
1:low ambient
temperature head
)ressure control
installed
0: No low ambient
temperature head
)ressure control
1: low ambient
temperature head
)ressure control
installed
0: No low ambient
temperature head
)ressure control
1: low ambient
temperature head
)ressure control
installed
YES
NO
NO*
0*
NO
ENBL
0111
YES
NO*
NO*
NO
NO
NO
WATER
WATER
55
290
21.6
21.6
21.6
2.0
Number of
degrees added
to brine freeze
set point to enable
cooler heater.)
NO
NO
14
55*
2.0
0.4
0.2
20*
100"
*Not supported.
ENTRY
ON/OFF
US/METR
Air-Cooled
YES
NO/YES
NO/YES
NO
0
NO/YES
ENBL/DSBL
YES
NO
NO/YES
NO/YES
NO/YES
YES/NO
WATER/BRINE
WATER/BRINE
55 F
21.6 F
21.6 F
21,6 F
2F
NO/YES
NO/YES
55*
2.0
0.4
0.2
2O%
100%
CL-3