ECON JUMPER SETTING
If the jumper for  MISC2 and MISC3 is set to ECON, the corresponding 
MISC screw terminal on the backplate will be connected to an economizer.
ECONOMIZER OPERATION - If your HVAC unit is equipped with an 
     economizer system, the thermostat will provide power to the MISC1, MISC2, 
     or MISC3 terminal of the thermostat when the thermostat is in an occupied 
     time period.  The MISC1, MISC2, or MISC3 terminal will be de-energized 
     when the thermostat is in an unoccupied time period.  
 
 
 
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a
second stage of cooling. 
Y2 OPERATION - SECTION 13 of the Owner’s Manual
Control up to two Cool stages.
 
 
The 2nd Stage of heat or cool is turned on when:
      (A) The 1st Stage has been on for the time required (step #27, 
            page 13.6).  It is adjustable from 0-60 minutes and the default 
            is two minutes.
 
      (B) The temperature spread from the setpoint is equal to or greater
            than: the setpoint plus the deadband (step #24, page 13.5), plus 
            the 2nd deadband (step #25, page 13.5).  This 2nd deadband is 
            adjustable from 0-10 degrees and the default is two degrees. 
 
 
 
Page 3.5
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
And
Cool
Setpoint
DeadbandDeadband
db 1 db 2
(adj. 0-10 )(adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
Cooling
TEMPERATURE
INCREASE