SYMPTOM: When controlling a residential heat pump, 
          and asking for cooling, the heat comes on.
CAUSE: The thermostat reversing valve jumper is set 
          for “b”.
REMEDY: Set the reversing valve jumper for “O”.  See 
          pages 5.4 and 5.5. 
SYMPTOM: When calling for cooling, both the heat 
          and cool come on.
CAUSE: The thermostat equipment jumper is configured 
          for “HP” and the HVAC unit is a Gas/Electric.
REMEDY: Set the equipment jumper for “Gas”.  See 
          pages 5.2 and 5.3.
8
TroubleShootingTroubleShooting
NOTE:  Due to the Random Start feature, outputs may not energize for up to 30 
             seconds when the thermostat is first powered (see page 16.4 of the 
             Owner’s Manual)