Programming Occupied & Unoccupied Periods
17
PROGRAMMING NOTES
You will be prompted to enter both heat and cool setpoints even if the 
thermostat is congured for heat only, or cool only.  
• Ifonly1Occupiedperiodisselected,theOccupied2&3stepswillbeskipped.
Further, if only 2 occupieds are selected, the Occupied 3 steps will be skipped. 
• Heat&CoolsetpointsforOccupied1arethesameforeachday.Heat&
CoolsetpointsforOccupied2&3canbeadjusteddierentlyforeachday,if
desired.
• If the start time is set for later than the stop time, the program will 
run from the start time to midnight and from midnight to the stop time 
on the same day. For example:  9:00pm start, 8:00am stop, on MTWTF.  This 
program will run from 12:00am MTWTF to 8:00am MTWTF and again from 
9:00pm MTWTF to 12:00pm MTWTF.
• TheUnoccupiedsettingstakeeectatalltimeswhen:(1)theprogramis
on and (2) the current time is outside a preset occupied period. For this 
reason start and stop times aren’t necessary for unoccupied.
• Ifthesame start and stop times are programmed in for an occupied 
period, then it will run 24 hours.
• Ifoneoccupiedperiodstartsandstopswithinanotheroccupiedperiod,the
lower occupied # has priority.  For example:  If Occupied 3 is programmed 
to be “on” 24 hours, and Occupied 2 is programmed to run  that day, then 
Occupied 2 settings will take over from Occupied 3 between Occupied 2 
start and stop times.
• WhenthetimeperiodprogrammingforUnoccupiedisintheOverride
mode(seepage12),theHeat&CoolsetpointsforOccupied1areused.
Downloaded from ManualsNet.com search engine