REMARKS:
Use a multimeter to test the DC voltage between the 2 port (or S or L2 port) and the 3 port (or N or S port) of the outdoor unit.
The red pin of the multimeter connects to the 2 port (or S or L2 port) while the black pin is for 3 port (or N or S port).
When the air conditioner is running normally, the voltage is moving alternately as positive values and negative values.
If the outdoor unit malfunctions, the voltage has always had a positive value.
If the indoor unit malfunctions, the voltage has always had a certain value.
Use a multimeter to test the reactor resistance which does not connect with a capacitor.
The normal value should be around zero ohm. Otherwise, the reactor has malfunctioned.
NOTE: Images and the values inside are for reference only. Actual condition and specific value may vary.