PC 0F(PFC Module Protection Diagnosis and Solution)
Description: When the voltage signal that the IPM sends to the compressor drive chip is abnormal, the LED displays the failure
code and the air conditioner turns off.
Recommended parts to prepare:
• Connection wires
• Inductance
• Outdoor main PCB
• PFC module
Troubleshooting and repair:
Test the resistance between every two ports of U, V, W of IPM and P, N. If any of the ports result is 0 or close to 0, the IPM is defective.
Otherwise, follow the procedure described on the following flowchart.
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the voltage
between P and N is normal
refer to the index
No
goo
,
two ports is
Check whether the
inductance of PFC module is
good. If the inductance is
good, the resistance of the
two ports is 0
Yes
No
Connect it tightly , check
normal or not
Replace the outdoor main boardYes
Yes
No
No
Replace the PFC module
Trouble is solved