EasyManua.ls Logo

Carrier 38MHRCQ12AA3 - Test the DC Voltage; Test the Reactor Resistance

Carrier 38MHRCQ12AA3
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SG-38MHRC-01 Specifications subject to change without notice. 33
DIAGNOSIS AND SOLUTION (CONT)
Fig. 38 — Test the DC Voltage
Use a multimeter to test the DC voltage between the outdoor unit’s L2 port and S port. The red pin of the multimeter connects with the L2
port while the black pin is for the S port. When the air conditioner is running normal, the voltage moves alternately between -50V to 50V. If the
outdoor unit malfunctions, the voltage moves alternately with positive value. If the indoor unit malfunctions, the voltage has a certain value.
Fig. 39 — Test the Reactor Resistance
Use a multimeter to test the resistance of the reactor which does not connect with the capacitor. The normal value should be around zero (0)
ohm. Otherwise, the reactor has a malfunction and needs to be replaced.

Table of Contents

Related product manuals