No. Item Outline of specifications Remarks
4
Air speed
selection
(Continued):
Item code
[5d]
Standard Type 1 Type 3 Type 6
0136
SW501 (1)/(2) OFF/OFF ON/OFF OFF/ON ON/ON
Tap COOL COOL COOL COOL
F1 HH HH
F2 HH
F3 H+ H+, H
H+, H
L+, L
F4
F5
HH
H
F6 L+
F7 H+ L
F8 H L+
F9 L
FA L+
FB L
FC
FD UL UL UL UL
3)
In automatic cooling operation, the revolution frequency
of (HH) is set larger than that in the standard cooling
operation.
Ta
(°C)
F4F5
F5
47
42
4) Self-clean operation
When performing self-clean operation after stopping
the cooling operation, the mode becomes [UL]
(210 rpm).
Selection of high
ceiling type
Item code:
[5d] or selection of
high ceiling on P.C.
board SW501
However only when
the high ceiling
selection is set to
[Standard]
[Self-clean
] is
displayed.
0131UP 0181UP 0241UP 0251UP 0301UP 0361UP 0401UP 0481UP 0601UP
F1 610 610 630 630 700 700 700 700 700
F2 550 550 590 590 670 670 670 670 670
F3 490 500 530 530 660 660 660 660 660
F4 430 450 470 470 640 640 650 650 650
F5 400 400 450 450 620 620 640 640 650
F6 390 390 440 440 610 610 630 630 650
F7 370 370 410 410 550 550 560 560 600
F8 350 350 380 380 490 490 490 490 590
F9 340 340 370 370 480 480 480 480 570
FA 330 330 350 350 450 450 460 460 550
FB 320 320 330 330 420 420 430 430 520
FC 310 310 320 320 400 400 420 420 500
FD 250 250 250 250 300 300 300 300 300
Tap
Revolution speed (rpm)
- 36 -