EasyManua.ls Logo

Carrier 40TGV0481UP - Page 37

Carrier 40TGV0481UP
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item
5.
Capacity
control
Operation flow and applicable data, etc.
The cooling capacity depending on the load is adjusted.
ture and the room temperature, the capacity is adjusted by
the compressor revolution.
Description
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
3) The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
4) According to the difference
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commuta-
tion timing are varied.
5) Change the compressor motor
speed by outputting power to the
compressor.
* The contents of control
operation are same in cooling
operation.
Set temp. (Ts)
Room temp. (Ta)
Correction of Hz signal
Detection of electromotive force
of compressor motor winding
Detection of motor speed and rotor position
In
verter output change
Commutation timing change
Change of compressor speed
Remote controller Indoor unit
Ts –Ta
Correction value of Hz signal Operating Hz
According to difference between the setup value of tempera-
- 37 -

Other manuals for Carrier 40TGV0481UP

Related product manuals