No. Item Outline of specifications Remarks
8
Louver control
(Continued):
<<Selection of Swing mode>>
For the Swing mode, the following three types of modes
are selectable and settable by keeping Swing/Direction
button pushed for 4 seconds or more on the remote
controller.
1 Standard (4 pieces: same phase) swing
Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align
at the horizontal discharge position and then start
the Swing operation at the same time.
2 Dual swing Data: [0002]
When operation is selected, the louvers of louver
No. [01] and [03] move to the horizontal discharge
position, the louvers of louver No. [02] and [04] move
to the downward discharge position and then start
the Swing operation at the same time.
3 Cycle swing Data: [0003]
When operation is selected, the louver No. [01]
moves to the horizontal discharge position, [03] to
the downward discharge position, [02] and [04] to the
middle position and then start the Swing operation at
the same time.
Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
In case of selecting the Swing mode, “Dual swing” or
“Cycle swing”, the following numerals is displayed at
the center of the remote controller screen for approx.
3 seconds when
button was pushed to select
[SWING].
(No display for the standard swing)
Alternate lighting
(0.5 sec.)
Alternate lighting
(0.5 sec.)
<<Louver lock (Louver fix)>>
For the air direction setup for each discharge port,
the louver position can be locked during the normal
operation.
An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
button pushed for
4 seconds or more on the remote controller.
The louver lock can be set by registering the setup data
to Item code (DN) [F1] to [F4] according to the following
table.
Item code Objective louver No. Setup data
F1 01
0000: Release
(At shipment)
F2 02
0001: Horizontal
discharge position
F3 03
~
F4 04
0005: Downward
discharge position
Not possible to set
by wireless remote
controller.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
The standard swing
performs the same
swing operation as the
present operation
(2 series).
For the setting
operation, refer to [How
to set up type of the
swings] in Item “Setup
at local site/Others”.
Not possible to set
by wireless remote
controller.
Dual swing Cycle swing