No. Item Outline of specifications Remarks
8
Louver control
(Continued):
<<Selection of Swing mode>>
• For the Swing mode, the following three types of modes
are selectable and settable by keeping Swing/Direction
button pushed for 4 seconds or more on the remote
controller.
1 Standard (4 pieces: same phase) swing
→ Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align
at the horizontal discharge position and then start
the Swing operation at the same time.
2 Dual swing → Data: [0002]
When operation is selected, the louvers of louver
No. [01] and [03] move to the horizontal discharge
position, the louvers of louver No. [02] and [04] move
to the downward discharge position and then start
the Swing operation at the same time.
3 Cycle swing → Data: [0003]
When operation is selected, the louver No. [01]
moves to the horizontal discharge position, [03] to
the downward discharge position, [02] and [04] to the
middle position and then start the Swing operation at
the same time.
• Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
• In case of selecting the Swing mode, “Dual swing” or
“Cycle swing”, the following numerals is displayed at
the center of the remote controller screen for approx.
3 seconds when
button was pushed to select
[SWING].
(No display for the standard swing)
Alternate lighting
(0.5 sec.)
Alternate lighting
(0.5 sec.)
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port,
the louver position can be locked during the normal
operation.
• An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
button pushed for
4 seconds or more on the remote controller.
• The louver lock can be set by registering the setup data
to Item code (DN) [F1] to [F4] according to the following
table.
Item code Objective louver No. Setup data
F1 01
0000: Release
(At shipment)
F2 02
0001: Horizontal
discharge position
F3 03
~
F4 04
0005: Downward
discharge position
Not possible to set
by wireless remote
controller.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
The standard swing
performs the same
swing operation as the
present operation
(2 series).
For the setting
operation, refer to [How
to set up type of the
swings] in Item “Setup
at local site/Others”.
Not possible to set
by wireless remote
controller.
Dual swing Cycle swing