Function selection item No. (DN) list
DN Item Contents
At shipment from factory
01 Filter sign lighting time
0000: None 0001: 150H
0002: 2500H 0003: 5000H
0004: 10000H 0005: Clogging sensor used
According to type
02 Filter stain level
0000: Standard
0001: Heavy stain (Half of standard time)
0000: Standard
10 Type
0000: (1-way air discharge cassette)
0001: (4-way air discharge cassette) to 0037
According to model type
11 Indoor unit capacity 0000: Undecided 0001 to 0034 According to capacity type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Undecided
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Undecided
14 Group address
0000: Individual 0001: Master unit in group
0002: Follower unit in group
0099: Undecided
19
Louver type
(Adjustment of air direction)
0000: No louver model 0001: Swing only
(0002:1-way) (0003:2-way)
0004: 4-way
According to model type
1E
In automatic cooling/heating, temp.
width of cool
heat, heat
cool mode selection control point
0000: 0 deg to 0010: 10 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0003: 3 deg
(Ts±1.5)
28 Automatic reset of power failure 0000: None 0001: Provided
0001: Provided
2b
Selection of thermostat output
(T10 3 )
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Thermostat ON
2E Selection of HA (T10) terminal
0000: Normal (JEMA) 0001: Card input
0002: Fire alarm input (Forgotten to be off)
0000: Normal
(HA terminal)
31 Fan (Single operation) 0000: Impossible 0001: Possible 0000: Impossible
32 Sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body sensor
5d
High ceiling selection
(Air volume selection)
0000: Standard
0001: High ceiling (1)
0003: High ceiling (3)
0000: Standard
60
Timer setting (Wired remote
controller)
0000: Operable 0001: Operation prohibited 0000: Operable
42 Self-clean operation time
0000: None
0000: 0.5 h to 0012: 6h
Set when compressor-ON time is 10 to 60 minutes.
When ON-time is 60 minutes or more,
the double of this operation time setting is set.
0002: 1 hour
45
Selection of louver horizontal
discharge position
0000: Smudging-less setting
0002: Cold draft preventive setting
0000: Smudgingless
setting
C2 Current demand X% to outdoor unit 0050: 50% to 0100: 100% 0075: 75%
CC
Setting of self-clean operation forced
stop
0000: No
Clean operation is performed in case of stop by HA input.
HA operation output OFF during clean operation in case of
stop by remote controller
0001: Yes
Clean operation is not performed in case of stop by HA input.
HA operation output ON during clean operation in case of
stop by remote controller
0000: None