DN Item Contents
At shipment from factory
Cd
Clean operation stop function when
[ON/OFF] operation is prohibited.
The air conditioner stops (including fire alarm such as remot
monitor system) while setup of [ON/OFF] operation prohibited
(Central 1, 2) is performed from the central controller side.
0000: Valid (Clean operation)
0001: Invalid (No clean operation)
0000: Valid
d0
Existence of remote controller save
function
0000: Invalid (Impossible) 0001: Valid (Possible) 0001: Valid (Possible)
d3
Revolution frequency of self clean
operation
0000: Invalid (Self clean operation is not carried out.)
0001: Valid (Self clean operation is practiced with 210 rpm.)
0001: Valid
d4
Display / No display of
[Dry operation] during self clean
operation
0000: Display 0001: No display 0000: Display
F0 Louver swing mode
0000: No synchronization 0001: 4-way synchronization
0002: Dual 0003: Cycle
0001: 4-way
synchronization
F1 Louver No.1 fixed positio
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release
F2 Louver No.2 fixed positio
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release
F3 Louver No.3 fixed positio
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release
F4 Louver No.4 fixed positio
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release
* The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for sav
operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).
- 74 -