26
40VMH072 - 096 — 
Fig. 43 —Fan disassembly (072-096)
1. Remove the bottom cover plate. See Fig. 43.
2. Remove the 6 bolts from the front plate.
3. Support the fan sub-assembly from the bottom, then lift up and remove the fan sub-assembly.
4. After motor maintenance is complete, install the motor assembly in the reverse order of steps 1, 2 and 3 (steps 3, 2, and 1).
IMPORTANT: During this process, the indoor unit does not need to be removed.
INDOOR UNIT ADDRESSING
For proper system operation, each indoor unit must have a 
unique address set from 0 to 63. When setting an address by 
remote controller, outdoor units, indoor units, and MDC must 
be powered on. If “FE” appears on the LED screen or display 
board, this unit has no address. After setting all indoor units’ 
addresses, turn off the power supply to all indoor units to clear 
errors.
Indoor units’ addressing can be distributed automatically in the 
heat pump system. The heat recovery system cannot 
accomplish this function at this time. When dip switch “S6” 
on, the outdoor unit’s main PCB board is set to 00 (default set 
in factory), indoor units are set for auto-addressing. When 
powering on for the first time, it takes six minutes or more to 
finish auto-addressing each indoor unit.
motor 
assembly
bottom 
cover plate
screw
pothook
scroll
bolt