10
Step 6 — Position and Connect Controller
Wired  controllers  should  be  installed  in  a  position  that
maintains good temperature control:
• Position the thermostat approximately 48 in. above floor
level.
• Do  not  position  thermostat  where  it  can  be  directly
affected by the unit’s discharge airstream.
• Avoid external walls and drafts from windows and doors.
• Avoid  positioning  near  shelves  and  curtains  as  these
restrict air movement.
• Avoid  heat  sources  such  as  direct  sunlight,  heaters,
dimmer switches, and other electrical devices.
• See  Fig.  16  for  an  example  of  communication  wire
connection.
CONTROL WIRING 
1. The  communication  wire  should  be  2-core  stranded
shielded cable.
2. For  indoor  and  outdoor  unit  communication,  use  P,  Q
terminals. Shielded core should be used for ground.
3. Wiring should be run according to the wiring diagram.
4. Communication wire must not form a closed loop.
See Fig. 16.
Fig. 16 —Communication Wire Connection
OPTION/EXTENSIONS OF COMMUNICATION 
WIRING — To  extend  control  wiring  or  to  make  terminal
connections,  use  the  PQE  connection  wire  supplied  in  the
accessory kit and follow the steps below.
1. Cut the connector on the outdoor unit side as shown in
Fig. 17.
2. Strip a suitable length of the insulation layer as shown in
Fig. 18. 
Fig. 18 —Stripping The Wire
3. Use a suitable screwdriver to fix the communication wire
on the outdoor unit communication terminal as shown in
Fig. 19.
Fig. 19 —Connecting Communication Wire to 
Outdoor Unit Communication Terminal
If communication wires are used to connect indoor units, find
the corresponding port and plug it in directly as shown in Fig.
20.
Fig. 20 —Connecting the Communication Wires
If it is not possible to buy communication wires from Carrier,
connect the indoor unit side of communication wires using the
connector provided with the accessories as shown in Fig. 21.
See Figs. 22 and 23 for typical communication wiring of the
heat pump and the heat recovery systems.
Fig. 21 —Connecting the Communication Cable (Indoor Unit to Outdoor Unit) Using the Supplied Connector
LEGEND
ACB — Auxiliary Control Board
 To outdoor / indoor/ 
 MDC unit comm.bus 
To wired controller comm. bus
CAUTION
Failure to follow these procedures may result in personal
injury or damage to equipment.
NEVER CONNECT the main power source to the control
or communication terminal block.
USE AN APPROPRIATE SCREWDRIVER for 
tightening the terminal screws. Do not over tighten the 
terminal screws.
IMPORTANT:  Wiring  for  communication  shall  be  two
inches or more apart from power source wiring to avoid
electric  noise.  Do  not  insert  control/communication  and
power source wire in the same conduit.
Pay attention to polarity of the communication wire.
Connector in accessory kitConnector on indoor unit Communication cable
in field
Fig. 17 —Shearing Outdoor Connector