7
INSTALLING MOUNTING BRACKET AND MOUNT-ING
UNIT (FLOOR STANDING) — The mounting  bracket (see
Fig.  10)  can  be  anchored  to  the  wall  with  screws.  For  unit
weight and mounting dimensions, see Table 4.
Fig. 10 —Mounting Bracket Locations
Table 4 —Unit Weight and Mounting Dimensions 
(Floor Standing)
The  unit  can  now  be  lifted  and mounted  onto  the  mounting
brackets.
1. Anchor the brackets at the specified location on the wall
using the mounting screws. See Fig. 11.
2. Once the brackets are secured, lift the unit and mount it
on the brackets. Be sure the brackets are engaged in the
correct mounting locations on the back of the unit.
Fig. 11 —Mounting Brackets to Wall
For models 036 and 048 there is an outside air opening on the
back of the unit. See Fig. 12 below.
Fig. 12 —Outside Air Opening Cutout Location
Step 4 — Connect Piping
CONDENSATE PIPING  — The unit is supplied with a 5/8-
in.  OD  drain  connection  to  connect  copper  or  plastic  drain
piping.  When  installing  condensate  piping,  follow  these
recommendations:.
• Condensate  piping  should  slope  downward  in  the
direction of  condensate  flow, with  a minimum  gradient
of 1 in. per 100 inches.
• When  multiple  units  are  connected  to  a  common
condensate drain, ensure that the drain is large enough to
accommodate the volume of condensate from all units. It
is  also  recommended  to  have  an  air  vent  in  the
condensate piping to prevent any air locks.
• Condensate piping must not be installed where it may be
exposed to freezing temperatures.
REFRIGERANT PIPING
When connecting refrigerant piping from an indoor unit to an
outdoor unit, follow these guidelines:
• Check  maximum  height  drop  and  length  of  refrigerant
piping  between  the  indoor  and  outdoor  units.  If  the
difference  between  them  is  more  than  33  ft,  consider
mounting the outdoor unit above indoor unit.
• Refrigerant  piping  connection  between  indoor  and
outdoor  units  should  be  performed  once  the  units  are
secured at their respective installation locations.
• The refrigeration piping starts at the indoor unit and ends
at the outdoor unit.
• The number of bends in the refrigeration piping must be
fewer than 15.
• The refrigerant piping should be dry and free of dust and
other impurities.
• The  bending  angle  of  the  refrigerant  pipe  should  not
exceed 90
° and the bending radius should be as large as
possible to prevent any breakage in piping.
• Use proper cutting and flaring tools to avoid leakage.
• Before  insulating  the  suction  and  liquid  refrigeration
pipes,  perform  pressure  and  leak  tests.  For  details,  see
the  outdoor  unit  installation  manual.  Insulating  both
suction and liquid refrigerant pipes is required.
• Vacuuming and charging of the system should be carried
out as described in the outdoor unit installation manual.
40VMU UNIT WEIGHT (lb)
DIMENSION (in.)
A B
012 57 17-
7
/
8
19-
7
/
8
015-024 62 17-
7
/
8
19-
7
/
8
030 76 31-
1
/
4
19-
7
/
8
036,048 106 42-
1
/
8
17-
3
/
4
CAUTION
To avoid site damage, be sure there are no water, plumbing,
or electrical lines running through the wall at the mounting
location.
IMPORTANT: Be  sure to anchor the brackets on wall
studs.
CAUTION
Cut along the marked dotted line only. Failure to do so may
result in damage to the equipment.
CAUTION
When connecting from  an indoor unit to an outdoor unit,
the  isolation  valve  at  the  outdoor  unit  should  be  in  the
closed  position  throughout  the  refrigerant piping  process.
Failure  to  follow this procedure  may result in  equipment
damage.
please cut along the marked 
For outside air opening, 
dotted line.