CAUTION
•
Wrong wiring connection may cause some electrical parts burn out.
•
Be sure to comply with local rule on running the wire from indoor unit
to outdoor unit (size of wire and wiring method, etc.).
•
Every wire must be connected firmly.
•
If incorrect or incomplete wiring is carried out, it will cause an ignition
or smoke.
•
Prepare the power supply for exclusive use with the air conditioner.
•
This product can be connected to the mains.
Connection to fixed wiring : A switch which disconnects all poles and
has a contact separation of at least 3 mm must be incorporated in the
fixed wiring.
OTHERS
Gas Leak Test
Model 18 Class 22 Class
Power source
220-240V Single phase, 50Hz
220-230V Single phase, 60Hz
Maximum running current
10.0A
13.5A
Plug socket & fuse rating
13A
16A
Power cord H07RN-F or 60245 IEC66 (1.5 mm
2
or more)
NOTE : Connecting cable
•
Wire type : More than 1.5 mm
2
(H07RN-F or 60245 IEC66) or 1.3 mm
2
(AWG-16)
Test Operation
Auto Restart Setting
How to set the Auto Restart
1. Press and hold the [RESET] button on the indoor unit for 3 seconds to set
the operation. (3 beep sound and OPERATION lamp [
] blink 5 time/sec
for 5 seconds)
2. Press and hold the [RESET] button on the indoor unit for 3 seconds to
cancel the operation. (3 beep sound but OPERATION lamp [
] does not
blink)
•
In case of ON timer or OFF timer are set, AUTO RESTART
OPERATION does not activate.
This product is designed so that, after a power failure, it can restart
automatically in the same operating mode as before the power failure.
To switch the TEST RUN (COOL) mode, press [RESET] button for 10
seconds. (The beeper will make a short beep.)
RESET button
Information
The product was shipped with Auto Restart function in the off position.
Turn it on as required.
• Check the flare nut
connections for the gas
leak with a gas leak
detector or soap water.
Check places for
the indoor unit.
Check places for
the outdoor unit.
Remote Control A-B Selection
•
When two indoor units are installed in the same room or adjacent two
rooms, if operating a unit, two units may receive the remote control signal
simultaneously and operate. In this case, the operation can be preserved
by setting either one remote control to B setting. (Both are set to A setting
in factory shipment.)
•
The remote control signal is not received when the settings of indoor unit
and remote control are different.
•
There is no relation between A setting/B setting and A room/B room when
connecting the piping and cables.
To separate using of remote control for each indoor unit in case of 2 air
conditioners are installed near.
Remote Control B Setup.
1. Press [RESET] button on the indoor unit to turn the air conditioner ON.
2. Point the remote control at the indoor unit.
3. Push and hold [CHECK] button on the Remote Control by the tip of the
pencil. “00” will be shown on the display (Picture 1).
4. Press [MODE] during pushing [CHECK]. “B” will show on the display and
“00” will disappear and the air conditioner will turn OFF. The Remote
Control B is memorized (Picture 2).
Note : 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A have not “A” display.
3. Default setting of Remote Control from factory is A.
1 2
RESET
0
1
0
1
01
01
30
30
40
40
L
N
1
2
3
Stripping length of the connecting cable
Connecting cable
Power cord
Terminal block
Earth line
Connecting cable
Power cord
Earth line
NOTE
•
Wire type : H07RN-F or 60245 IEC66 (1.5 mm
2
or more)
Electrical Work
1. The supply voltage must be the same as the rated voltage of the air
conditioner.
2. Prepare the power source for exclusive use with the air conditioner.